English
Language : 

DRC-24V100W1AZ Datasheet, PDF (8/12 Pages) Delta Electronics, Inc. – Chrome DIN Rail Power Supply
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ
Safety Instructions
– ALWAYS switch mains of input power OFF before
connecting and disconnecting the input voltage to the
unit. If mains are not turned OFF, there is risk of
explosion / severe damage.
– To guarantee sufficient convection cooling, keep a
distance of 50mm above and below the device as well
as a lateral distance of 25mm to other units.
– Note that the enclosure of the device can become very
hot depending on the surrounding air temperature and
load of the power supply. Risk of burns!
– DO NOT insert any objects into the unit.
– Hazardous voltages may be present for up to 5 minutes
after the input mains voltage is disconnected. Do not
touch the unit during this time.
– The power supplies unit should be installed in minimum
IP54 rated enclosure.
– The power supplies are built in units and must be
installed in a cabinet or room (condensation free
environment and indoor location) that is relatively free of
conductive contaminants.
Functions
■ Graph illustrating the Start-up Time, Rise Time, and Hold-up Time
Start-up Time
The time required for the output voltage to reach 90% of its set value, after the input voltage is applied.
Rise Time
The time required for the output voltage to change from 10% to 90% of its set value.
Hold-up Time
Hold up time is the time when the AC input collapses and output voltage retains regulation for a certain period of time. The time
required for the output to reach 90% of its set value, after the input voltage is removed.
8
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (November 2013, Rev. 00)