DRR-20A Datasheet, PDF (6/6 Pages) Delta Electronics, Inc. – The new Redundancy Module DRR 20A is the latest offering from one of the World’s No.1 Power Supply Company.
CliQ II Redundancy Module 20A 40A
Redundancy Module
DRR- 20A
DRR- 40A
1.) INPUT DATA
Nominal input voltage
24-48VDC
Voltage range
Nominal current
20A max
22-60VDC
40A max
Input voltage alarm / relay contacts
24V system:
both Vin1 & Vin2 >18V +/- 5% or
<30V max. relay contacts
48V system:
both Vin1 & Vin2 >36V +/- 5% or
<60V max. relay contacts
Note: The LED will turn on when The Vin1 & Vin2 > 18V +/- 5% (For 24V system) or > 36V +/- 5% (For 48V system) and not
more than 30V (For 24V system) or not more than 60V (For 48V system), The relay contacts will be closed. If Vin1 & Vin2 is under
or over this range, The LED will be turn off.
2.) OUTPUT DATA
Nominal output voltage UN / tolerance
Nominal current
Vin-0.65V (Typ)
20A max / 40A max
Derating above +50 °C
> 50°C (2.5% / K.)
Short circuit / Over Load Limit
(<25A for DRR- 20A)
(<50A for DRR- 40A)
Note: The overload condition must be controlled by The PSUs in parallel; The limit of input current would not more than 25A (For
20A module) or not more than 50A (For 60A module).
Efficiency
> 97% typical.
3.) CERTIFICATION / STANDARDS
Electrical equipment of machines
IEC60204-1 (over voltage category III)
Electrical safety (information technology equipment)
UR/cUR recognized to UL60950-1, SIQ BG to EN60950-1, CB test certificate and report
to IEC60950-1 and CE.
Industrial Control Equipment
UL/cUL recognize to UL508
Electronic equipment for use in electrical power
installations
EN50178 / IEC62103
Safety entry low voltage
PELV (EN60204), SELV (EN60950)
RoHS Compliant
Yes, RoHS directive, WEEE directive
Protection against electric shock
DIN 57100-410
4.) GENERAL DATA
Isolation voltage:
Input / PE
test/routine test:
output / PE
test/routine test:
type
type
1.5 KVAC / 1.5 KVAC
1.5 KVAC / 1.5 KVAC
Degree of protection
IP20
Class of protection
Class II with PE connection
MTBF
> 800,000hrs. as per BELL CORE STD or IEC61709
Type of housing
Aluminium (AL1100F)
Dimensions (W / H / D) + mounting rail
121 mm X 50 mm X 122.1 mm (L X W X H)
Weight
0.375Kg
0.515Kg
LED (DC INPUT OK)
Vin1 OK and Vin2 OK (GREEN LED)
5.) CLIMATIC DATA
Ambient temperature (Operating)
Ambient temperature (Storage)
- 40°C to 80°C (> 50°C derating)
- 40°C to 85°C
Humidity at+25 °C, no condensation
< 95% RH
Vibration (Non-Operating)
10Hz to 500Hz @ 30 m/S2 (3G peak); displacement of 0.35mm; 60min per axis for all
X, Y, Z direction. Refer to IEC 60068-2-6. Note: all figures quoted are amplitudes (peak
values)
Shock (in all directions)
IEC60068-2-27, 30G (300m/s2) for duration 18ms 1 Shock in 2 Directions tested with
Fixture with EUT mounted on DINRAIL in Vertical and Horizontal position.
Pollution degree
2 according to EN50178
Climatic class
3K3 according to EN 60721
Conformance with EMC guideline
2004/108/EC and for low voltage guideline
2006/95/EC :
DRR-20A (EOE21010284)
DRR-40A(EOE21010285)
EMC (electromagnetic compatibility)
Immunity to interference :
According to EN 61000-6-2
CE (EMC and Low Voltage directive)
 EN 61000-4-2 1)
Discharge of static electricity (ESD)
Housing:
LEVEL 4
Contact discharge:
8 KV
Air Discharge:
15 KV
 EN 61000-4-3 1)
Radiate Field Immunity Housing:
LEVEL 3
Frequency/Field intensity:
80MHz - 1GHz / 10V/M with 1kHz tone / 80% modulation
 EN 61000-4-8 2)
Power frequency magnetic fields Input:
Level 3
Current:
10A/meter
EN55011 corresponds to CISPR11 / EN55022 corresponds to CISPR22 / EM 61000 corresponds to IEC 1000
1) Criterion A: Normal operating behavior within the defined limits.
2) Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
3) Symmetrical: Conductor to conductor.
4) Asymmetrical: Conductor to ground.
5) Class B:
Area of application industry and residential.
www.deltaPSU.com
6