English
Language : 

DRS-5V50W1AX Datasheet, PDF (4/13 Pages) Delta Electronics, Inc. – Sync DIN Rail Power Supply
TECHNICAL DATASHEET
Sync DIN Rail Power Supply
5V 50W Series / DRS-5V50W1A□ / DRS-5V50W1N□
Reliability Data
MTBF
Expected Cap Life Time
Safety Standards / Directives
Safety Entry Low Voltage
Electrical Safety
Industrial Control Equipment
Class 2 Power Supply
CE
Material and Parts
Galvanic Isolation
Model Number
DRS-5V50W1A☐
DRS-5V50W1N☐
Telcordia SR-332
MIL-HDBK-217F
> 700,000 hrs, I/P: 115Vac & 230Vac,
O/P: 100% load, Ta: 25°C
165,300 hrs, I/P: 115Vac & 230Vac,
O/P: 100% load, Ta: 25°C
10 years (115ac & 230Vac, 50% load @ 40°C)
TUV Bauart
UL/cUL recognized
CB Scheme
SELV (EN 60950)
EN 60950-1
UL 60950-1, CSA C22.2 No. 60950-1 (File No. E191395)
IEC 60950-1,
Limited Power Source (LPS, for DRS-5V50WN☐ only)
UL/cUL listed
UL/cUL recognized
UL 508 and CSA C22.2 No. 107.1-01 (File No. E315335)
UL 60950-1, CSA C22.2 No. 60950-1(File No. E191395)
(for DRS-5V50WN☐ only)
In conformance with EMC Directive 2014/30/EU and Low
Voltage Directive 2014/35/EU
Input to Output
Input to Ground
RoHS Directive 2011/65/EU Compliant
3.0KVac
3.0KVac
Output to Ground 0.5KVac
4
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
www.DeltaPSU.com (June 2016, Rev. 00)