MDS-100APS12BA Datasheet, PDF (3/10 Pages) Delta Electronics, Inc. – MDS Medical AC-DC Open Frame
T``E`CHNICAL DATASHEET
MDS Medical AC-DC Open Frame
12V100W / MDS-100APS12 BA
(a) 115V
Ripple & Noise measurement circuit
Fig. 2 Ripple & Noise example, 20MHz BW
(b) 230V
Mechanical
Case Chassis
Case Cover
Dimensions (W x Lx H)
Unit Weight
Terminal
Wire
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test (Non-Operating)
Vibration (Operating)
Input
Output
NA
NA
76.2X127X31mm(3X5X1.2 in)
0.21 kg
JST 2P
JST 8P
NA
Operating
Storage
-10°C to +70°C
-40°C to +85°C
-10°C to +50°C 100% load
50°C to 70°C de-rate power by 2.5% / °C, See Fig. 3
10-95% RH (Non-Condensing)
3,000 meters
50G, 11ms, 3 shocks for each direction
5-500Hz, 2.09Grms, 20 minute for each three axis
3
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (July 2013, Rev. 00)