TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
48V 240W 1 Phase / DRP048V240W1B□
Mechanical
Case Cover / Chassis
Dimensions (L x W x D)
Unit Weight
Indicator
Cooling System
Terminal
Wire
Mounting Rail
Noise (1 Meter from power supply)
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test (Non-Operating)
Vibration (Non-Operating)
Pollution Degree
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Degree of Protection
Protection Against Shock
*PE: Primary Earth
Reliability Data
MTBF
Expected Cap Life Time
Input
Output
Aluminium
121 x 85 x 124.1 mm
0.96 kg
Green LED (DC OK)
Convection
3 Pins (Rated 300V/15A)
4 Pins (Rated 300V/15A)
AWG 20-12
Standard TS35 DIN Rail in accordance with EN 60715
Sound Pressure Level (SPL) < 40dBA
Operating
Storage
Vertical Mounting
Horizontal Mounting
-25°C to +80°C
-25°C to +85°C
> 50°C de-rate power by 2.5% / °C
> 40°C de-rate power by 2.5% / °C
< 95% RH (Non-Condensing)
2,500 Meters
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
1 times per direction, 2 times in total
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction
2
< 57V, SELV Output, Hicc-up Mode,
Non-Latching (Auto-Recovery)
> 150% of rated load current, Hicc-up Mode,
Non-Latching (Auto-Recovery)
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Hicc-up Mode, Non-Latching
(Auto-Recovery when the fault is removed)
IP20
Class I with PE* connection
> 500,000 hrs. as per Telcordia SR-332
I/P: 115Vac, O/P: 100% load, Ta: 25°C
10 years (400Vac & 500Vac, 50% load @ 40°C)
3
All parameters are specified at 25°C ambient unless otherwise noted.