English
Language : 

DRC-24V30W1AZ Datasheet, PDF (3/12 Pages) Delta Electronics, Inc. – Chrome DIN Rail Power Supply
TECHNICAL DATASHEET
Chrome DIN Rail Power Supply
24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test (Operating)
Vibration (Operating)
Pollution Degree
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Degree of Protection
Protection Against Shock
*PE: Primary Earth
Reliability Data
MTBF
Expected Cap Life Time
Operating -25°C to +71°C
Storage -25°C to +85°C
> 55°C de-rate power by 2.5% / °C
5 to 95% RH (Non-Condensing)
0 to 2,000 Meters
IEC 60068-2-27, Half Sine Wave: 4G for a duration of
22ms, 3 shocks for each 3 directions, 9 times in total
IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G
peak); 10 min per cycle, 60 min for all X, Y, Z directions
2
< 34.8V, SELV Output, Latch-off Mode
> 130% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery)
> 75°C Surrounding Air Temperature @ 100% load,
Latch-off Mode
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
IP20
Class II (No PE* connection is required)
> 500,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C
10 years (115Vac & 230Vac, 50% load @ 40°C)
3
All parameters are specified at 25°C ambient unless otherwise indicated.
www.DeltaPSU.com (April 2014, Rev. 00)