TECHNICAL DATASHEET
PMC Panel Mount Power Supply
24V 150W 1 Phase / PMC-24V150W1B□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
DC Input Voltage Range*
Input Current
Efficiency at 100% Load
Max Inrush Current (Cold Start)
Power Factor
Leakage Current
* Fulfills test conditions for DC input. Safety approval for DC input can be obtained upon request.
100-240Vac
85-264Vac
50-60Hz
47-63Hz
125-375Vdc
< 1.70A @ 115Vac, < 1.00A @ 230Vac
> 89% @ 115Vac, > 91% @ 230Vac
< 60A @ 115Vac, < 120A @ 230Vac
> 0.99 @ 115Vac, > 0.90 @ 230Vac
< 1mA @ 240Vac
Output Ratings / Characteristics**
Nominal Output Voltage
Factory Set Point Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
PARD*** (20MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
24Vdc
24Vdc ± 2%
22-28Vdc
6.25A (150W max.)
150W
< 0.5% typ. (@ 85-264Vac input, 100% load)
< 1% typ. (@ 85-264Vac input, 0-100% load)
< 100mVpp
< 30ms @ nominal input (100% load)
< 3000ms @ nominal input (100% load)
> 30ms @ 115Vac & 230Vac (100% load)
± 5% @ 85-264Vac input, 0-100% load
(Slew Rate: 0.1A/μS, 50% duty cycle @ 5Hz to 100Hz)
8,000µF Max
**For power de-rating from 50°C to 70°C, see power de-rating on page 3.
. ***PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1µF ceramic capacitor & 47µF electrolytic capacitor
2
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.