English
Language : 

DRP048V120W1BA Datasheet, PDF (2/16 Pages) Delta Electronics, Inc. – CliQ II DIN Rail Power Supply
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
48V 120W 1 Phase / DRP048V120W1B□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
Nominal DC Input Voltage
DC Input Voltage Range*
Input Current
Efficiency at 100% Load
Max Inrush Current
Power Factor
Leakage Current
*Fulfills tested conditions
Output Ratings / Characteristics
Nominal Output Voltage
Output Voltage Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
PARD (20MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
100-240Vac
85-264Vac
50-60Hz
47-63Hz
125-250Vdc
120-375Vdc
< 2.20A @ 115Vac, < 1.10A @ 230Vac
> 90.0% @ 115Vac, > 91.0% @ 230Vac
< 35A @ 115Vac, < 50A @ 230Vac
> 0.99 @ 115Vac, > 0.93 @ 230Vac
< 1mA @ 240Vac
48Vdc
± 1% (initial set point tolerance from factory)
48-56Vdc
2.50A (continuously operating at 48V)
3.75A (Power Boost for 5 seconds at 48V, refer to the
details in the Functions section)
120W (continuously operating)
180W (Power Boost for 5 seconds, refer to the details in
the Functions section)
< 0.5% typ. (@ 320-600Vac input, 100% load)
< 1% typ. (@ 320-600Vac input, 0-100% load)
< 200mVpp
< 200ms @ nominal input (100% load)
< 2,000ms @ nominal input (100% load)
> 20ms @ 115Vac,
> 50ms @ 230Vac (100% load)
± 2% @ 0-100% load
6,500µF Max
2
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 01)