English
Language : 

DRP024V120W1BX Datasheet, PDF (2/15 Pages) Delta Electronics, Inc. – Power will not de-rate for the entire input voltage range
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 120W 1 Phase / DRP024V120W1B□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
DC Input Voltage Range*
Input Current
Efficiency at 100% Load
Max Inrush Current (Cold Start)
Leakage Current
**Fulfills the test conditions for DC input. DC input safety approval can be obtained upon request.
100-240Vac
85-264Vac
50-60Hz
47-63Hz
120-375Vdc
< 2.20A @ 115Vac, < 1.10A @ 230Vac
> 89.0% @ 115Vac, > 90.0% @ 230Vac
< 35A @ 115Vac & 230Vac
< 1mA @ 240Vac
Output Ratings / Characteristics
Nominal Output Voltage
Output Voltage Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
PARD (20MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
24Vdc
± 2% (initial set point tolerance from factory)
24-28
5.00A (continuously operating at 24V)
7.50A (Power Boost for 5 seconds at 24V, refer to the
details in the Functions section)
120W (continuously operating at 24V)
180W (Power Boost for 5 seconds at 24V, refer to the
details in the Functions section)
< 0.5% typ. (@ 85-264Vac input, 100% load)
< 1% typ. (@ 85-264Vac input, 0-100% load)
< 150mVpp
< 100ms @ nominal input (100% load)
< 1,000ms @ nominal input (100% load)
> 20ms @ 115Vac,
> 115ms @ 230Vac (100% load)
± 5% @ 0-100% load
10,000µF Max
2
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.