English
Language : 

DRP024V060W1BN Datasheet, PDF (2/12 Pages) Delta Electronics, Inc. – CliQ II DIN Rail Power Supply
TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 60W 1 Phase / DRP024V060W1B□
Specifications
Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
Nominal Input Frequency
Input Frequency Range
Nominal DC Input Voltage
DC Input Voltage Range
Input Current
Efficiency
Max Inrush Current
Power Factor
Leakage Current
100-240Vac
85-264Vac
50-60Hz
47-63Hz
125-250Vdc
120-375Vdc
< 1.40A @ 115Vac, < 0.80A @ 230Vac
> 90.0% @ 115Vac & 230Vac
< 20A @ 115Vac, < 35A @ 230Vac
Conform to EN61000-3-2
< 1mA @ 240Vac
Output Ratings / Characteristics
Nominal Output Voltage
Output Voltage Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
Residual Ripple / PARD (20MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response (Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
24Vdc
± 2% (initial set point tolerance)
24-28Vdc
2.5A
60W
< 0.5% typ. (@ 85-264Vac input, 100% input)
< 1% typ. (@ 85-264Vac input, 0-100% input)
< 50mVpp / <150mVpp @ 25°C
< 100ms @ nominal input (100% load, 25°C)
< 2000ms @ nominal input (100% load, 25°C)
> 20ms @ 115Vac,
> 125ms @ 230Vac (100% load, 25°C)
± 5% @ 10-100% load
8,000µF Max
2
All parameters are specified at 25°C ambient unless otherwise noted.
www.DeltaPSU.com (September 2013, Rev. 02)