English
Language : 

AA60S Datasheet, PDF (2/6 Pages) Delta Electronics, Inc. – 60W Single AC/DC Power Module
Output Characteristics
Parameter
Output Voltage Accuracy
Line Regulation
Load Regulation
Ripple & Noise (20MHz)
Conditions
Vin=Min. to Max.
Iout=Min. to Max.
5.1VDC Output Models
Other Output Models
Min.
Typ.
Max.
Unit
---
±1.0
±2.0
%
---
±0.2
±1.0
%
---
±0.5
±1.0
%
%VPP of
---
2.0
3.0
%VPP of
---
1.0
1.3
Minimum Load
Over Voltage Protection
Transient Response Deviation
Temperature Coefficient
Overshoot
Current Limitation
Short Circuit Protection
---
10
Zener diode clamp
---
120
(Iout=100% to Iout=50%)
±3
---
±0.02
---
---
Foldback, auto-recovery
(long term overload condition may cause damage)
105
---
Hiccup mode, indefinite (automatic recovery)
---
%Inom.
---
% of Vo
±6
%
---
%/℃
5
% Vout
---
%Inom.
General Characteristics
Parameter
Conditions
Min.
Typ.
Max.
Unit
I/O Isolation Voltage
Input to Output, 60 Seconds
3000
---
---
VACrms
I/O Isolation Resistance
500 VDC
100
---
---
MΩ
Switching Frequency
---
100
---
KHz
Hold-up Time
---
20
---
ms
MTBF (calculated)
EMC Emission
MIL-HDBK-217F@25℃, Ground Benign
Conducted and radiated
125,000
---
---
Hours
EN 55011 class B, EN 55022 class B, FCC part 15 class B
Standard
Specification Requirement
Performance
Criteria
EN61000-4-2
Air ±8KV Cont. ±4KV
B
EN61000-4-3
80~1000MHz, 10V/m 80% AM, 1KHz modulation
A
EMC Immunity according
EN61000-6-1
EN61000-4-4
EN61000-4-5
AC port ±2KV DC, SL, TL ±2KV not less than 1
B
min.
1.2/50μS(8/20μS) AC dif. ±1KV DC ±0.5KV
B
0.15~80MHz, 10Vrms (functional earth ports
EN61000-4-6
included)
B
80% AM, 1KHz modulation
EN61000-4-8
50Hz/60Hz, 30A/m
A
EN61000-4-11
30%, 10ms
B
60%, 100ms, 95%, 5000ms
C
Protection Class II
According IEC/EN 60536
Safety Approvals
cUL/UL 60950-1,IEC/EN 60950-1
UL508 approval
Input Fuse
Built-in Fuse
External Fuse (Recommended)
All Models
6A / 250VAC
3A Slow – Blow Type
DS_AA60S_06172014
E-mail: DCDC@delta.com.tw
http://www.deltaww.com/dcdc P2