DS18S20-PAR Datasheet, PDF (1/20 Pages) Dallas Semiconductor – 1-Wire® Parasite-Power Digital Thermometer | |||
|
www.dalsemi.com
FEATURES
⢠Unique 1-wire interface requires only one
port pin for communication
⢠Derives power from data line (âparasite
powerâ)âdoes not need a local power supply
⢠Multi-drop capability simplifies distributed
temperature sensing applications
⢠Requires no external components
⢠±0.5°C accuracy from â10°C to +85°C
⢠Measures temperatures from â55°C to
+100°C (â67°F to +212°F)
⢠9-bit thermometer resolution
⢠Converts temperature in 750 ms (max.)
⢠Userâdefinable non-volatile temperature
alarm settings
⢠Alarm search command identifies and
addresses devices whose temperature is
outside of programmed limits (temperature
alarm condition)
⢠Ideal for use in remote sensing applications
(e.g., temperature probes) that do not have a
local power source
DS18S20-PAR
1-Wire® Parasite-Power
Digital Thermometer
PIN ASSIGNMENT
DALLAS
18S20P
123
123
(BOTTOM VIEW)
TO-92
(DS18S20-PAR)
PIN DESCRIPTION
GND - Ground
DQ - Data In/Out
NC - No Connect
DESCRIPTION
The DS18S20-PAR digital thermometer provides 9âbit centigrade temperature measurements and has an
alarm function with nonvolatile user-programmable upper and lower trigger points. The DS18S20-PAR
does not need an external power supply because it derives power directly from the data line (âparasite
powerâ). The DS18S20-PAR communicates over a 1-wire bus, which by definition requires only one
data line (and ground) for communication with a central microprocessor. It has an operating temperature
range of â55°C to +100°C and is accurate to ±0.5°C over a range of â10°C to +85°C.
Each DS18S20-PAR has a unique 64-bit identification code, which allows multiple DS18S20-PARs to
function on the same 1âwire bus; thus, it is simple to use one microprocessor to control many
DS18S20-PARs distributed over a large area. Applications that can benefit from this feature include
HVAC environmental controls, temperature monitoring systems inside buildings, equipment or
machinery, and process monitoring and control systems.
1 of 20
043001
|
▷ |