English
Language : 

VDR-120-48 Datasheet, PDF (1/2 Pages) CUI INC – Single Output DIN Rail Power Supply
•
VDR-120-48 Single Output DIN Rail Power Supply
Features
·Low cost
·105°C output capacitor
·AC Input range selected by switch
·High efficiency, low working temperature
·Soft-start circuit, limiting AC surge current
·Short circuit, overload, over-voltage protected
·Compact size, light weight
·100% full load burn-in test
·Built in EMI filter, low ripple noise
·Din rail mountable
DC output voltage
Output V. tolerance
Output rated current
Output current range
Ripple & noise
Line regulation
Load regulation
DC output power
Efficiency
DC voltage adj.
Input voltage range
AC current
Inrush current
Leakage current
Overload protection
Over voltage protection
Over temp. protection
Temperature coefficient
Set up, rise, hold up time
Vibration
Withstand voltage
Isolation resistance
Working temp., humidity
Storage temp., humidity
Dimensions
Weight
Safety standards
EMC standards
48V
±1%
2.5A
0-2.5A
100mVp-p
±0.5%
±1%
120W
85%
48-53V
88~132VAC/176~264VAC selected by switch, 47~63Hz; or 254~370VDC
2.8A/115V 1.7A/230V
cold start 30A/115V 60A/230V
<3.5mA/240VAC
105%~150%
type: constant current limiting, auto recovery
58~65V
90 ºC ± 5°C type: shutdown and auto-restart
±0.03% / °C (0~50°C)
500ms;70ms; 30ms/230V,115V
10~500Hz, 2G 10min./1cycle (1 hour each axes)
I/P-O/P: 3KVAC, I/P-FG: 1.5KVAC, O/P-FG: 0.5KVAC, for 1 min.
I/P-O/P, I/P-FG, O/P-FG: 500VDC / 100M Ohms min.
-10°C~+60% (refer to output derating curve), 20%-90% RH
-20ºC~+85ºC, 10%~95% RH
2.58x4.93x3.94 inches (65.5x125.2x100mm)
1.76 lbs (0.8Kgs)
TUV EN60950, UL508
EN55022 CLASS B, EN61000-4-2,3,4,5,6,8,11; ENV50204, EN61000-3-2,-3
Notes:
1. All parameters are specified at 230VAC input, rated load, 25°C 70% ambient
2. Tolerance includes set up tolerance, line regulation, load regulation
3. Ripple & noise are measured at 20MHz by using a 12” twisted pair terminated with a 0.1uF & 47 uF capacitor
4. Line regulation is measured from low line to high line at rated load
5, Load regulation is measure from 0% to 100% rated load
*V-Infinity reserves the right to make changes to its products or to discontinue any product or service without notice, and to advise cus-
tomers to verify the most up-to-date product information before placing orders. V-Infinity assumes no liability or responsibility for cus-
tomer’s applications using V-Infinity products other than repair or replacing (at V-I’s option) V-Infinity products not meeting V-I’s pub-
lished specifications. Nothing will be covered outside of standard product warranty.
V-Infinity, LLC, 9615 SW Allen Blvd Suite 103, Beaverton, OR 97005
www.v-infinity.com 1-866-372-1258