English
Language : 

XTV121100_17 Datasheet, PDF (1/1 Pages) CSB Battery Co., Ltd. – Valve Regulated Lead Acid Battery
XTV series
XTV 121100 12V 110AH
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
Design for Standby Power Applications at Extreme Temperatures
【Design Life】
Up to 12 Years in Standby Service at 25℃
Eurobat (20℃) : 10-12 years, Long Life
【 Operating Temperature Range】
Nominal Operating Temperature : 25℃(77℉)
Discharge : -20℃ ~ 50℃ (-4℉~122℉)
Charge: -20℃ ~ 50℃ (-4℉~122℉)
Storage: -15℃ ~ 40℃ (5℉~104℉)
【 Float Charging Voltage】
13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
【Equalization Charging Voltage 】
14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
【 Self Discharge】
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored
at higher temperature than 25℃ (77℉).
Specification Design according with IEC 60896-21/22:2004
Nominal Voltage
12V (6 cells per unit)
Nominal Capacity
110 Ah @20hr-rate to 1.75V per cell @25℃ (77℉)
Weight
Approx. 34.20 Kg (75.38lbs)
Maximum Discharge Current
800A (5sec)
Internal Resistance
Approx. 3.60 mΩ
Short Circuit Current
2648A
Maximum Charge Current
33A
Terminal types
I2 thread lead alloy terminal to accept M6 bolt
Terminal hardware Torque
138.6 Kgf-cm / 120.3 Lbf-in / 13.58 N-m
Container Material
PP (UL 94-HB) & Flame Retardant (94-V0) available upon request
Length (L)
343.0±2.5 mm
13.50±0.10 inch
Dimensions
Width (W)
Container Height (h)
170.0±2.0 mm
213.9±2.5 mm
6.69±0.08 inch
8.42±0.10 inch
Overall Height (H)
216.9±2.5 mm
8.54±0.10 inch
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5 MIN
425
382
364
339
289
231
10MIN
307
289
276
254
232
200
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
15MIN 30MIN 60MIN 90MIN
2HR
3HR
5HR
235
138
78.6
55.8
43.7
31.2
20.0
227
135
77.5
55.4
43.5
30.8
19.9
222
134
77.2
55.0
43.0
30.7
19.7
207
130
75.6
54.0
42.5
30.3
19.5
188
123
72.3
52.1
41.2
29.4
18.9
163
114
67.1
48.8
38.9
28.2
18.2
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time 5 MIN 10MIN 15MIN 30MIN 60MIN 90MIN
2HR
3HR
5HR
1.60V
4173
3108
2509
1543
890
640
505
363
236
1.67V
3921
2975
2418
1515
884
635
502
361
235
1.70V
3745
2914
2368
1508
880
633
501
359
234
1.75V
3384
2783
2251
1464
862
622
493
356
231
1.80V
2988
2573
2053
1411
827
600
479
346
228
1.85V
2719
2220
1834
1323
773
567
455
334
218
Please refer to the official site for the lastest rating confirmation. URL: www.csb-battery.com
Sales Offices
8HR
10HR
20HR
13.1
10.7
5.53
13.0
10.6
5.52
12.9
10.5
5.51
12.8
10.4
5.50
12.6
10.2
5.33
12.0
9.86
5.15
8HR
10HR
20HR
155
126
66.7
154
125
66.6
153
124
66.1
152
123
65.7
149
122
64.9
145
118
62.3
Issued: 161101
Recognized under UL 1989,
and certified by ISO 9001, 14001.
BUSINESS HEADQUARTERS
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
USA OFFICE
Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872)
Fax: +1-817-244-4445
SHENZHEN OFFICE (CHINA)
Tel: +86-755-8831-6488, 8831-6775
Fax: +86-755-8831-6075
EUROPE (EMEA) OFFICE
Tel: +31(0)180-418-140
Fax: +31(0)180-418-327
SHANGHAI OFFICE (CHINA)
Tel: +86-21-5046-1622, 5046-0833
Fax: +86-21-5046-1046
TAIPEI OFFICE
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
BEIJING OFFICE (CHINA)
Tel: +86-10-5820-5336, 5820-5338
Fax: +86-10-5820-3053