English
Language : 

XTV121000_17 Datasheet, PDF (1/1 Pages) CSB Battery Co., Ltd. – Valve Regulated Lead Acid Battery
XTV series
XTV 121000 12V 100AH
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
Design for Standby Power Applications at Extreme Temperatures
【Design Life】
Up to 12 Years in Standby Service at 25℃
Eurobat (20℃) : 10-12 years, Long Life
【 Operating Temperature Range】
Nominal Operating Temperature : 25℃(77℉)
Discharge : -20℃ ~ 50℃ (-4℉~122℉)
Charge: -20℃ ~ 50℃ (-4℉~122℉)
Storage: -15℃ ~ 40℃ (5℉~104℉)
【 Float Charging Voltage】
13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
【Equalization Charging Voltage 】
14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
【 Self Discharge】
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored
at higher temperature than 25℃ (77℉).
Specification Design according with IEC 60896-21/22:2004
Nominal Voltage
12V (6 cells per unit)
Nominal Capacity
100 Ah @20hr-rate to 1.75V per cell @25℃ (77℉)
Weight
Approx. 30.20 Kg (66.56 lbs)
Maximum Discharge Current
800A (5sec)
Internal Resistance
Approx. 4.10 mΩ
Short Circuit Current
2258A
Maximum Charge Current
30A
Terminal types
I2 thread lead alloy terminal to accept M6 bolt
Terminal hardware Torque
138.6 Kgf-cm / 120.3 Lbf-in / 13.58 N-m
Container Material
PP (UL 94-HB) & Flame Retardant (94-V0) available upon request
Length (L)
308.7±2.5 mm
12.15±0.10 inch
Dimensions
Width (W)
Container Height (h)
169.0±2.0 mm
210.6±2.5 mm
6.65±0.08 inch
8.29±0.10 inch
Overall Height (H)
213.6±2.5 mm
8.41±0.10 inch
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5 MIN
371
328
309
282
243
191
10MIN
259
242
231
212
193
170
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
15MIN 30MIN 60MIN 90MIN
2HR
3HR
5HR
194
116
67.8
48.9
38.7
27.7
17.7
188
114
67.2
48.7
38.4
27.4
17.5
184
113
66.7
48.3
38.0
27.3
17.4
173
110
65.5
47.7
37.6
26.9
17.3
157
104
63.0
46.3
36.5
26.1
16.8
138
96.9
59.1
43.8
34.6
25.2
16.1
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time 5 MIN 10MIN 15MIN 30MIN 60MIN 90MIN
2HR
3HR
5HR
1.60V
3591
2638
2095
1307
778
569
450
323
211
1.67V
3382
2513
2029
1286
775
567
447
321
210
1.70V
3268
2445
1987
1274
771
564
445
319
209
1.75V
2932
2308
1880
1245
761
557
440
316
207
1.80V
2572
2149
1727
1192
735
545
429
308
203
1.85V
2255
1872
1546
1125
695
519
412
297
194
Please refer to the official site for the lastest rating confirmation. URL: www.csb-battery.com
Sales Offices
8HR
10HR
20HR
11.6
9.54
5.05
11.5
9.47
5.02
11.4
9.45
5.01
11.3
9.38
5.00
11.2
9.16
4.84
10.7
8.82
4.63
8HR
10HR
20HR
138
114
59.9
137
113
59.6
136
112
59.3
135
111
59.0
133
110
58.1
129
105
55.9
Issued: 161101
Recognized under UL 1989,
and certified by ISO 9001, 14001.
BUSINESS HEADQUARTERS
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
USA OFFICE
Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872)
Fax: +1-817-244-4445
SHENZHEN OFFICE (CHINA)
Tel: +86-755-8831-6488, 8831-6775
Fax: +86-755-8831-6075
EUROPE (EMEA) OFFICE
Tel: +31(0)180-418-140
Fax: +31(0)180-418-327
SHANGHAI OFFICE (CHINA)
Tel: +86-21-5046-1622, 5046-0833
Fax: +86-21-5046-1046
TAIPEI OFFICE
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
BEIJING OFFICE (CHINA)
Tel: +86-10-5820-5336, 5820-5338
Fax: +86-10-5820-3053