English
Language : 

UPS123606 Datasheet, PDF (1/2 Pages) CSB Battery Co., Ltd. – specially designed for high efficient discharge application
Powered by
UPS123606
Specification
UPS 123606 is specially designed for high efficient discharge
application. Its characteristics are high energy density, small
footprint and high discharge efficiency. It can be used for more
than 260 cycles at 100% discharge in cycle service, up to 5 years
in standby service.
Cells Per Unit
Voltage Per Unit
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging
Current Limit
Equalization and Cycle Service
Self Discharge
Terminal
Container Material
6
12
360W @ 5min-rate to Watt(1.60V)/pcs @25 (77 )
7.5 A h @ 20hr-rate to 1.75V per pcs @25 (77 )
Approx. 1.97 kg(4.34 lbs)
100/130A(5sec)
Approx. 22m
Discharge: -15 ~50 ( 5 ~122 )
Charge: -15 ~40 ( 5 ~104 )
Storage: -15 ~40 ( 5 ~104 )
25 3 (77 5 )
13.5 to 13.8 VDC/unit Average at 25 (77 )
3.0A
14.4 to 15.0 VDC/unit Average at 25 (77 )
CSB Batteries can be stored for more than 6 months at
25 (77 ). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
F1/F2-Faston Tab 180/250
ABS(UL 94-HB/File E50263)*Flammability resistance of
(UL 94-V0/File E88637) can be available upon request.
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL924 and UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
Dimensions :
Unit: mm (inch)
Overall Height (H)
98.3±1 (3.87±0.04)
Container height (h)
94±1 (3.7±0.04)
Length (L)
151±2 (5.94±0.08)
Width (W)
51±1 (2.01±0.04)
Sealed Lead Battery. Battery must be
recycled. For recycling information
Inside the USA call (800) Re-Use-Pb (738-7372)
Outside the USA call 1 (817) 244-4415
(http://www.csb-battery.com)
5
The system of manufacturer was certified
by URS according to ISO 9001,ISO 14001.
CSB BATTERY(GUANG ZHOU)CO., LTD.
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
Constant Current Discharge Characteristics Unit:A (25 ,77 )
2MIN
59.0
53.6
50.4
46.2
39.6
33.5
3MIN
47.1
43.4
41.4
37.9
34.1
30.5
4MIN
40.2
37.3
35.9
32.9
30.1
27.6
5MIN
34.8
32.2
31.2
29.0
26.8
24.5
6MIN
30.6
28.7
27.8
26.2
24.5
22.7
7MIN
27.3
26.2
25.3
24.0
22.5
20.9
8MIN
24.8
23.9
23.3
22.2
20.8
19.4
10MIN
21.3
20.7
20.3
19.6
18.5
17.1
15MIN
15.7
15.3
15.0
14.7
14.1
13.3
20MIN
12.9
12.8
12.6
12.2
11.9
10.9
30MIN
9.07
8.99
8.81
8.63
8.60
8.14
60MIN
5.18
5.16
5.12
5.07
4.96
4.71
90MIN
3.64
3.60
3.56
3.49
3.42
3.29
Constant Power Discharge Characteristics Unit:W (25 ,77 )
2MIN
577
543
521
470
420
388
3MIN
471
448
431
403
375
335
4MIN
414
390
377
352
330
307
5MIN
360
338
330
311
293
273
6MIN
323
308
300
288
274
258
7MIN
295
284
278
267
254
235
8MIN
270
262
258
250
239
217
10MIN
235
232
227
220
210
192
15MIN
176
174
172
169
161
149
20MIN
143
142
140
137
133
124
30MIN
104
103
101
99.7
98.1
94.4
60MIN
60.5
60.2
59.9
59.5
58.0
55.8
90MIN
42.7
42.3
41.8
41.2
40.5
39.4
RA: 0812