GPL series
GPL 12400 12V 40AH
Valve Regulated Lead Acid Battery
Maintenance-Free Sealed Lead Acid Battery.
Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99%.
Design for Standby Power Applications
【Design Life】
Up to 10 Years in Standby Service at 25℃
Eurobat (20℃) : 10-12 years, Long Life
【 Operating Temperature Range】
Nominal Operating Temperature : 25℃(77℉)
Discharge : -15℃ ~ 50℃ (5℉~122℉)
Charge: -15℃ ~ 40℃ (5℉~104℉)
Storage: -15℃ ~ 40℃ (5℉~104℉)
【 Float Charging Voltage】
13.5 ~ 13.8 VDC/Unit at 25℃ (77℉)
【Equalization Charging Voltage 】
14.4 ~ 15.0 VDC/Unit at 25℃ (77℉)
【 Self Discharge】
Less than 10% after 90 days, can be stored up to 6 months at 25℃ (77℉);
Fully recharging is required before usage, and charged sooner if stored
at higher temperature than 25℃ (77℉).
Specification
Nominal Voltage
Nominal Capacity
Weight
Design according with IEC 61056-1/2:2012
12V (6 cells per unit)
40 Ah @20hr-rate to 1.75V per cell @25℃ (77℉)
Approx. 14.50 Kg (31.96 lbs)
Maximum Discharge Current
400A (5sec)
Internal Resistance
Short Circuit Current
Maximum Charge Current
Approx. 6.4mΩ
--
12.00A
Terminal type
Terminal hardware Torque
Container Material
B8-L terminal to accept M5 bolt
59.0 Kgf-cm/ 51.0 Ibf-in/ 5.73 N-m
ABS (UL 94-HB) & Flame Retardant (94-V0) available upon request
Length (L)
197.0±2.0 mm
7.76±0.08 inch
Dimensions
Width (W)
Container Height (h)
Overall Height (H)
165.0±2.0 mm
170.4±2.0 mm
170.4±2.0 mm
6.50±0.08 inch
6.71±0.08 inch
6.71±0.08 inch
F.V/Time
1.60V
1.67V
1.70V
1.75V
1.80V
1.85V
5MIN
162
145
137
124
111
98.1
10MIN
103.5
96.5
92.8
87.4
81.3
75.1
Constant Current Discharge Characteristics Unit: A (25℃, 77℉)
15MIN 30MIN 60MIN 90MIN
2HR
3HR
5HR
78.2
47.7
28.1
20.4
16.3
11.6
7.36
74.5
46.7
27.9
20.3
16.2
11.5
7.34
72.4
46.1
27.8
20.2
16.1
11.4
7.32
69.5
45.0
27.6
20.1
16.0
11.3
7.29
65.9
43.8
27.4
19.9
15.9
11.2
7.25
62.4
42.5
27.0
19.8
15.8
11.1
7.22
Constant Power Discharge Characteristics Unit: W (25℃, 77℉)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN
2HR
3HR
5HR
1.60V
1941
1242
938
572
338
245
195
139
88.4
1.67V
1735
1158
895
558
335
243
194
138
88.1
1.70V
1647
1117
869
552
334
242
193
137
87.9
1.75V
1490
1049
830
539
331
241
192
136
87.5
1.80V
1334
975
791
525
328
239
191
135
87.2
1.85V
1178
902
749
510
324
238
190
134
86.7
Please refer to the official site for the lastest rating confirmation. URL: www.csb-battery.com
Sales Offices
8HR
10HR
20HR
4.83
3.93
2.03
4.77
3.85
1.94
4.75
3.82
1.91
4.69
3.76
1.84
4.62
3.70
1.77
4.56
3.64
1.70
8HR
10HR
20HR
58.0
47.2
24.4
57.3
46.4
23.3
57.0
46.0
22.9
56.3
45.2
22.1
55.6
44.4
21.3
54.8
43.7
20.6
Issued: 161101
Recognized under UL 1989,
and certified by ISO 9001, 14001.
BUSINESS HEADQUARTERS
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
USA OFFICE
Tel: +1-817-244-7777 / 1-(800)3-CSB-USA (272872)
Fax: +1-817-244-4445
SHENZHEN OFFICE (CHINA)
Tel: +86-755-8831-6488, 8831-6775
Fax: +86-755-8831-6075
EUROPE (EMEA) OFFICE
Tel: +31(0)180-418-140
Fax: +31(0)180-418-327
SHANGHAI OFFICE (CHINA)
Tel: +86-21-5046-1622, 5046-0833
Fax: +86-21-5046-1046
TAIPEI OFFICE
Tel: +886-2-2880-5600
Fax: +866-2-2888-3300
BEIJING OFFICE (CHINA)
Tel: +86-10-5820-5336, 5820-5338
Fax: +86-10-5820-3053