English
Language : 

GP12200_16 Datasheet, PDF (1/2 Pages) CSB Battery Co., Ltd. – Cells Per Unit 6 Voltage Per Unit 12
Powered by
GP 12200 12V 20Ah
Specification
GP 12200 is a general purpose battery up to 5 years in standby
service or more than 260 cycles at 100% discharge in cycle
service. As with all CSB batteries, all are rechargeable, highly
efficient, leak proof and maintenance free.
Cells Per Unit
Voltage Per Unit
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging
Current Limit
Equalization and Cycle Service
Self Discharge
Terminal
Container Material
6
12
20 Ah @ 20hr-rate to 1.75V per cell @25°C (77°F)
Approx. 6.4 kg(14.11 lbs)
230A(5sec)
Approx. 13 mΩ
Discharge: -15°C~50°C ( 5°F~122°F)
Charge: -15°C~40°C ( 5°F~104°F)
Storage: -15°C~40°C ( 5°F~104°F)
25°C±3°C (77°F±5°F)
13.5 to 13.8 VDC/unit Average at 25°C (77°F)
6A
14.4 to 15.0 VDC/unit Average at 25°C (77°F)
CSB Batteries can be stored for more than 6 months at
25°C (77°F). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
I1-Thread lead alloy recessed terminal to accept M5 bolt
ABS(UL 94-HB) & Flammability resistance of
(UL 94-V0) can be available upon request.
TUV Asia Pacific Ltd.
Taiwan Branch
TUV Asia Pacific Ltd.
Taiwan Branch
CSB-manufactured VRLA
(Absorbent Glass Mat type)
batteries are UL-recognized
components under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
Dimensions :
Unit: mm (inch)
Overall Height (H)
167±2 (6.57±0.08)
Container height (h)
167±2 (6.57±0.08)
Length (L)
181±2 (7.13±0.08)
Width (W)
76.2±1 (3.0±0.04)
(http://www.csb-battery.com)
The system of manufacturer was certified
by TUV CERT according to ISO 9001,ISO 14001.
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR
1.60V
87.5 55.5 42.3 25.5 15.1 11.0 8.75 6.23 3.97 2.62 2.10
1.67V
77.7 51.8 39.7 24.9 15.0 10.9 8.69 6.22 3.94 2.60 2.07
1.70V
73.5 50.2 38.7 24.7 14.9 10.9 8.67 6.20 3.93 2.60 2.05
1.75V
66.4 47.0 37.1 24.2 14.8 10.7 8.54 6.17 3.92 2.59 2.03
1.80V
59.3 43.8 35.2 23.8 14.5 10.6 8.42 6.12 3.91 2.58 2.00
1.85V
52.2 40.5 33.7 23.2 14.3 10.4 8.29 6.07 3.90 2.57 1.96
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR
3HR
5HR
8HR 10HR
1.60V
1050 666
507
306
181
132
105
74.7
47.6
31.4
25.2
1.67V
932
621
481
301
179
130
104
74.6
47.3
31.3
24.9
1.70V
882
602
466
299
178
129
103
74.3
47.2
31.2
24.8
1.75V
797
564
446
292
176
128
102
74.0
47.1
31.1
24.4
1.80V
712
525
421
285
174
126
101
73.4
46.9
31.0
24.0
1.85V
627
487
404
278
171
125
100
72.8
46.8
30.9
23.6
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
20HR
1.09
1.04
1.03
1.00
0.96
0.92
20HR
13.1
12.5
12.3
11.9
11.5
11.1
RA1503