DRC3R48D420 Datasheet, PDF (4/12 Pages) Crydom Inc., – DRC Series
DataDINsRhaileMeoutnt
SWITCHING FREQUENCY/LOAD CHARACTERISTIC FOR ALL DEVICES
IL : Load Operating Current
IR : Rated Full Load Current [FLA]
ID : Direct-On-Line Inrush Current
tL : Load Operating Current Time
tD : Direct-On-Line Inrush Current Time
tC : Cycle Time
tOn : On Time
tOff : Off Time
ID
tD
tL
tOn
IL
IR
tOff
tC
MAXIMUM ALLOWABLE NUMBER OF STARTS PER HOUR DEPENDING ON THE STARTING
TIME tD AND THE ON PERIOD tOn (as for standard IEC 60947-4-2) FOR ALL DEVICES
Without overload relay (limit given by the contactor itself)
Table 1
• High inrush current (ID/IR = 4 to 7.2)
• Full load (IL/IR= 1)
Table 2
• High inrush current (ID/IR = 4 to 7.2)
• 60% load (IL/IR= 0.6)
Table 3
• Low inrush current (ID/IR < 4 )
• Full load (IL/IR= 1)
Table 4
• Low inrush current (ID/IR < 4 )
• 60% load (IL/IR= 0.6)
tOn (sec)
tD (sec) 0.1
1
0.05 5000 2700
10 100
350 35
0.1 3200 1950 350 35
0.2
- 950 320 35
0.4
- 500 280 35
0.8
- 290 160 35
1.6
-
-
110 30
3.2
-
-
75 25
tOn (sec)
tD (sec) 0.1
1
10 100
0.05 6000 3550 350 35
0.1 4100 3000 350 35
0.2
- 1300 350
35
0.4
-
700 320
35
0.8
-
400 320
35
1.6
-
- 125 35
3.2
-
-
90
35
tOn (sec)
tD (sec) 0.1
1
10 100
0.05 7450 3200 350 35
0.1 4050 2100 350 35
0.2
- 1200 350 35
0.4
- 650 320 35
0.8
- 350 280 35
1.6
-
-
180
35
3.2
-
-
90
35
tOn (sec)
tD (sec) 0.1
1
10 100
0.05 9000 3550 350 35
0.1 5400 3550 350 35
0.2
- 1700 350 35
0.4
- 850 350 35
0.8
- 560 350 35
1.6
-
-
240
35
3.2
-
-
180
35
With overload relay (limit given by the overload relay itself)
Table 5
• High inrush current (ID/IR = 4 to 7.2)
• Full load (IL/IR= 1)
Table 6
• High inrush current (ID/IR = 4 to 7.2)
• 60% load (IL/IR= 0.6)
tOn (sec)
tD (sec) 0.1
1
0.05 2200 1650
10 100
330 30
0.1 1500 1000 280 28
0.2
- 550 255 26
0.4
- 250 150 24
0.8
-
80
60 20
1.6
-
-
40 16
3.2
-
-
tOn (sec)
tD (sec) 0.1
1
10 100
0.05 2800 1800 320 35
0.1 1700 1300 310 32
0.2
-
650 290
30
0.4
-
300 200
26
0.8
- 200 90
25
1.6
-
-
65
25
3.2
-
-
-
-
Table 7
• Low inrush current (ID/IR < 4 )
• Full load (IL/IR= 1)
tOn (sec)
tD (sec) 0.1
1
10 100
0.05 5150 2800 260 35
0.1 2850 1920 250 34
0.2
- 1100 250 33
0.4
-
600 200 32
0.8
-
320 200 30
1.6
-
-
120 25
3.2
-
-
75
20
Table 8
• Low inrush current (ID/IR < 4 )
• 60% load (IL/IR= 0.6)
tOn (sec)
tD (sec) 0.1
1
10 100
0.05 5600 3200 350 35
0.1 3200 2700 350 35
0.2
-
1400 350
35
0.4
-
700 350 35
0.8
-
350 280 35
1.6
-
-
170 35
3.2
-
-
80
25