English
Language : 

H12WD4890PG Datasheet, PDF (3/7 Pages) Crydom Inc., – H12WD Series
DatasPahneleMeoutnt
MECHANICAL SPECIFICATIONS (5)
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
1.1
[27.9]
0.49
[12.4]
Screw Termination
Mounting
Hole/Slot
0.19 [4.9]
DIA.
1.88
[47.6]
1
OUTPUT
2
SOLID STATE RELAY
4
INPUT
3
1.7
[43.2]
Hex Standoff Termination (“K” Option) (3)
0.89
[22.6]
1.1
[27.9]
0.49
[12.4]
Mounting
Hole/Slot
0.19 [4.9]
DIA.
1.04
[26.4]
2.25
[57.3]
1.88
[47.6]
1
OUTPUT
2
SOLID STATE RELAY
4
INPUT
3
1.70
[43.2]
2.25
[57.3]
1.0
[25.4]
1.75
[44.5]
Quick Connect Termination (“F” Option) - Up to 25 Amp (2)
Mounting
Hole/Slot
0.19 [4.9]
DIA.
1.58
[40.2]
0.49
[12.4]
Faston Terminal(13)
0.25 x 0.032
(2 places)
1.31
[33.4]
1.88
[47.6]
1
OUTPUT
2
SOLID STATE RELAY
4
INPUT
3
1.7
[43.2]
2.25
[57.3]
1.0
[25.4]
1.75
[44.5]
0.93
[23.6]
(4 places)
1.0
[25.4]
(2 places)
Quick Connect Termination (“F” Option) - Up to 50 Amp (2)
Mounting
Hole/Slot
0.19 [4.9]
DIA.
1.58
[40.2]
0.63
[16.0]
Faston Terminal(13)
0.25 x 0.032
(4 places)
0.45
[11.4]
(2 places)
1.31
[33.4]
1.88
[47.6]
1
OUTPUT
2
SOLID STATE RELAY
4
INPUT
3
1.7
[43.2]
2.25
[57.3]
1.40
[35.6]
1.75
[44.5]
Faston Terminal(13)
0.187 x 0.020
(2 places)
1.25
[31.8]
0.49
[12.4]
1.40
[35.6]
1.75
[44.5]
Faston Terminal(13)
0.187 x 0.020
(2 places)
1.25
[31.8]
GENERAL NOTES
(1) Output will self trigger between 900-1200Vpk, Min. power factor 0.7 or higher, not suitable for capacitive loads.
(2) Single pair (up to 25A) Double pair* (50A model only). *Caution: User must connect to both pairs
(3) Option “K” is designed and tested for use with printed circuit boards or ring/fork terminals having a thickness between 0.031 and 0.093 inches (0.79 to 2.36 mm), and loads rated up to 50 Amps.
For higher load currents, the “K” standoff temperature must not exceed 105°C. For additional application assistance please contact Crydom Technical Support.
(4) Instantaneous turn-on version is not recomended for capacitive loads. Use zero turn-on only.
(5) All parameters at 25°C unless otherwise specified.
(6) Heat sinking required, see derating curves.
(7) Increase minimum voltage by 1V for operations from -20 to -40°C.
(8) Turn-on time for Instantaneous turn-on versions is 0.02 msec.
(9) All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report).
(10) Load can be wired to either SSR output terminal 1 or 2.
(11) Elective Input Status LED, “G” option.
(12) Elective Overvoltage Protection, “P” option.
(13) Mechanical dimensions vary from G3 models.
For additional information or specific questions, contact Crydom Technical Support.
Do not forget to visit us at: www.crydom.com