INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Must Turn-Off Voltage
Min Input Current @ Min Voltage (AC/DC) (for on-state)
Maximum Input Current @ Maximum Voltage
Nominal Input Impedance
Wire Size min-max (solid/stranded) [AWG/ IEC mm²] (4)
LED Status Indicator (Color)
Input Terminal Screw Torque [in lb (Nm)]
Maximum turn-on/off time
GENERAL SPECIFICATIONS
Description
Dielectric Strength, Input/Output/Base (50/60Hz)
Minimum Insulation Resistance (@ 500 V DC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Housing Material
Terminal Finish
Humidity
RoHS Exemption #’s
Agency Approval
GENERAL NOTES
GENERAL NOTES
1) All parameters at 40°C and per section unless otherwise specified.
2) See derating curves.
3) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
4) For UL Listing, must use wire rated @ 75°C
5) For DC output model minimum current spec is 15.7/12.4ma (AC/DC).
6) For DC output model maximum current spec is 27.9/20.3ma (AC/DC).
7) For DC output model, spec is 1K.
8) For DC output model, spec is 2500V
9) Activation Time = 65 ms / Deactivation Time = 100 ms
DRTxxxD06
12-24 VAC/DC
1 VAC/DC
7.6/6.3 mA (5)
12.1/9.1 mA (6)
2K (7)
22-16 / 0.33-1.31
Yes (green)
4.4 (0.5)
See note 9
DRTx24A06
180-280 VAC/DC
20 VAC/DC
7.2/7.1 mA
9.7/9.6 mA
25K
22-16 / 0.33-1.31
Yes (green)
4.4 (0.5)
See note 9
Parameters
3750 Vrms (8)
109 Ohm
10 pF
-30 to 80 °C
-40 to 125 °C
1.76 oz (50 g)
UL 94 V0 Self-extinguishing
Sulfamate Nickel
5 - 85% Non condensing
5(a), 7(a), 7(c)-I
UL 508 Listed, E116949
DRTx24B06
90-140 VAC/DC
10 VAC/DC
7.6/7.4 mA
12.5/12.3 mA
12K
22-16 / 0.33-1.31
Yes (green)
4.4 (0.5)
See note 9