English
Language : 

DC60S3_12 Datasheet, PDF (2/5 Pages) Crydom Inc., – panel mount
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Minimum Turn-On Voltage (3)
Minimum Turn-Off Voltage (4)
Typical Input Current
Nominal Input Impedance
Maximum Turn-On Time [msec] (5)
Maximum Turn-Off Time [msec] (6)
GENERAL SPECIFICATIONS
DC60Sx
3.5-32 VDC
3.5 VDC
1.0 VDC
2.2 mA @ 5 VDC
1500 Ohm
0.1
0.3
DC60SAx
90-280 Vrms/VDC
90 Vrms/VDC
10 Vrms/DC
2 mA @ 120 V, 4 mA @ 240 V
60K
10
40
Description
Dielectric Strength, Input/Output/Base (50/60Hz) [Vrms]
Minimum Insulation Resistance (@ 500 V DC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Encapsulation
Terminals
Recommended Terminal Screw Torque Range:
Parameters
4000
109 Ohm
8 pF
-30 to 80°C
-40 to 125 °C
3.0 oz (86.5g)
Thermally conductive Epoxy
Screws and Saddle Clamps Furnished, Unmounted
6-32 Screws - 10 in lbs. 8-32 and 10-32 Screws -20 in. lbs. (Screws dry without grase)
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) Heat sinking required, see derating curves.
3) Minimum turn-on voltage for –B, DC control is 1VDC and AC control is 10Vrms/VDC.
4) Minimum turn-off voltage for –B, DC control is 3.5VDC and AC control is 90Vrms/VDC.
5) Turn-on time for –B version is 300 µs
6) Turn-off time for –B version is 100 µs.
MECHANICAL SPECIFICATIONS