English
Language : 

CMD2425_11 Datasheet, PDF (2/5 Pages) Crydom Inc., – Panel Mount
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Maximum Reverse Voltage
Minimum Turn-On Voltage
Minimum Turn-Off Voltage
Maximum Input Current
Typical Input current
Maximum Turn-On Time [msec] (4)
Maximum Turn-Off Time [msec]
GENERAL SPECIFICATIONS
Description
Dielectric Strength, Input/Output/Base (50/60Hz)
Minimum Insulation Resistance (@ 500 VDC)
Maximum Capacitance, Input/Output
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Status Indicating Display
Weight (typical)
Encapsulation
Terminals
Maximum Wire Size-Output:
Maximum Wire Size-Input:
Recommended Terminal Screw Torque Range:
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
3) HEAT SINKING REQUIRED, FOR DERATING curves see page 2.
4) Turn-on time for DC control random turn-on versions is 0.02msec
5) Input circuitry incorporates active current limiter
CMD
3-32 VDC
32 VDC
3.0 VDC
1.0 VDC
30 mA
17 mA @ 5 VDC
1/2 Cycle
1/2 Cycle
CMA
90-140 Vrms
-
90 Vrms
10 Vrms
-
15 mA @ 120 Vrms
10
40
Parameters
4000 Vrms
109 Ohm
8 pF
-40 to 80 °C
-40 to 125 °C
Green LED
3.0 oz (86.5 g)
Thermally conductive Epoxy
Cage type
AWG 8 (3.8mm)
AWG 12 (2.5mm)
Output: 10-15 in lb (1.1-1.7 Nm)
Input: 5-6 in lb (0.6-0.7 Nm)