English
Language : 

PCV Datasheet, PDF (1/5 Pages) Crydom Inc., – Proportional controller
PCV Series
• Proportional controller
• Ratings from 15A to 90A @ 240 VAC
• 2-7 V DC or 2-10 V DC analog input range
PRODUCT SELECTION
Description
2-7 VDC Control
2-10 VDC Control
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-63Hz) [Vrms]
Transient Overvoltage [Vpk]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2)
Maximum Load Current (3) [Arms]
Minimum Load Current [Arms]
Maximum Surge Current (16.6ms) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum I² t for Fusing (8.3 msec) [A² sec]
Minimum Power Factor (with Maximum Load)
INPUT SPECIFICATIONS (1)
Description
Control Voltage Range
Typical Input Current @ 5 VDC
GENERAL SPECIFICATIONS
Description
Dielectric Strength, Signal to Load (50/60Hz)
Dielectric Strength, Signal to Base
Ambient Operating Temperature Range
Ambient Storage Temperature Range
Weight (typical)
Encapsulation
Terminals
GENERAL NOTES
1) All param eters at 25°C unless otherwise specified.
15 A
7PCV2415
10PCV2415
25 A
7PCV2425
10PCV2425
50 A
10PCV2450
75 A
10PCV2475
90 A
10PCV2490
100-240
600
10
200
15
0.15
150
1.6
94
0.5
100-240
600
10
200
25
0.15
250
1.6
260
0.5
100-240
600
10
200
50
0.15
625
1.6
1620
0.5
100-240
600
10
200
75
0.15
1000
1.6
4150
0.5
100-240
600
10
200
90
0.15
1200
1.6
6000
0.5
2-7 VDC
4 mA
2-10 VDC
4 mA
Parameters
2500 Vrms
2500 Vrms
-30 to 80 °C
-40 to 125 °C
3.5 oz. (100g)
Themaly Conductive Epoxy
Screws and Saddle clamps Furnished, Unmounted