H16WD Series
• Ratings from 25A to 90A @ 48-660 V AC
• 1600 Volt Blocking
• SCR output for heavy industrial loads
• DC control
• Zero-crossing (resistive loads) or random-fire (inductive loads) output
• Optional LED Status Indicator
PRODUCT SELECTION
Control Voltage
25A
4-32 Vdc
H16WD6025
AVAILABLE OPTIONS
50A
H16WD6050
75A
H16WD6075
90A
H16WD6090
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-440Hz) [Vrms]
Transient Overvoltage [Vpk]
Rated Load Current (2) [Arms]
Rated Load Current {UL508 Motor Controller} (2) [Arms]
Minimum Load Current [mArms]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (3)
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
Maximum I²t for Fusing (50/60Hz) [A² sec]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
HP rating UL 508/IEC60947[HP (KW)]: 240 VAC
HP rating UL 508/IEC60947[HP (KW)]: 380 VAC
HP rating UL 508/IEC60947[HP (KW)]: 480 VAC
HP rating UL 508/IEC60947[HP (KW)]: 600 VAC
Wire Size max (solid/stranded) [AWG/ IEC mm²]
Output Terminal Screw Torque Range [in lb (Nm)
25A
48-660
1600
25
10
150
1.0
500
239/250
285/259
1.02
1.6
1.5 (1.1)
2 (1.5)
3 (2.2)
3 (2.2)
2 x 8/8.4
18-20 (2-2.2)
50A
48-660
1600
50
20
150
1.0
500
597/625
1779/1621
0.63
1.6
3 (2.2)
5 (3.7)
5 (3.7)
10 (7.4)
2 x 8/8.4
18-20 (2-2.2)
75A
48-660
1600
75
30
150
1.0
500
954/1000
4555/4150
0.31
1.6
5 (3.7)
7.5 (5.6)
10 (7.4)
15 (11.2)
2 x 8/8.4
18-20 (2-2.2)
90A
48-660
1600
90
45
150
1.0
500
1145/1200
6560/5976
0.28
1.6
7.5 (5.6)
15 (11.2)
20 (14.9)
25 (18.6)
2 x 8/8.4
18-20 (2-2.2)