English
Language : 

D2410FPG-10 Datasheet, PDF (1/8 Pages) Crydom Inc., – Series 1 240 VAC
DatasPahneleMeoutnt
Series 1 240 VAC
• Ratings from 10A to 125A @ 24-280 VAC
• SCR output for heavy industrial loads
• Zero voltage or instantaneous turn-on outputs
• UL/CSA/VDE Approved, CE Compliant to EN60950-1
• Improved SEMS screw and washer
• Redesigned housing with anti-rotation barriers
For Generation 3 datasheet click here
• AC or DC control
• Direct bond copper substrate
• EMC compliant to Level 3
• Direct power lead frame
• Epoxy free design
PRODUCT SELECTION
Control Voltage
3-32 VDC
90-280 VAC
18-36 VAC
10A
D2410
A2410
A2410E
25A
D2425
A2425
A2425E
50A
D2450
A2450
A2450E
75A
D2475
A2475
A2475E
90A
D2490
A2490
A2490E
110A
D24110
A24110
A24110E
125A
D24125
A24125
A24125E
AVAILABLE OPTIONS
Control Voltage
A: 90-280 VAC
D: 4-32 VDC
AxxxxE: 18-36 VAC
A 24 10 E
Operating
Rated Load Current
Voltage
10: 10 Amps
24: 24-280 VAC 25: 25 Amps
50: 50 Amps
75: 75 Amps
90: 90 Amps
110: 110 Amps
125: 125 Amps
Overvoltage Protection
Blank: Not Included
P: Included (3)
Snubber
Blank: Not Included
S: Included
Switching Type
Blank: Zero Voltage Turn-On
-10: Instantaneous Turn-On (4)
K P G S H -10
Termination
Blank: Screw
F: Quick Connect (1)
(Up to 50 Amps only)
K: Hex standoffs (2)
Input Status LED
Blank: Not Included
G: Included
Thermal Pad
Blank: Not Included
H: Included
Required for valid part number
For options only and not required for valid part number
* Not all part number combinations are available.
Contact Crydom Technical support for information on
the availability of a specific part number.
OUTPUT SPECIFICATIONS (5)
Description
Operating Voltage (47-440Hz) [Vrms] (6)
Transient Overvoltage [Vpk]
Maximum Off-State Leakage Current @ Rated Voltage [mArms] (7)
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]
Maximum Load Current [Arms] (2)(8)
Minimum Load Current [mArms]
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vrms]
Thermal Resistance Junction to Case (Rjc) [°C/W]
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]
Minimum Power Factor (at Maximum load) (3)
10A
24-280
600
1
500
10
150
115/120
1.15
1.03
66/60
0.5
25A
24-280
600
1
500
25
150
239/250
1.15
0.8
285/259
0.5
50A
24-280
600
1
500
50
150
597/625
1.15
0.45
1770/1621
0.5
75A
24-280
600
1
500
75
150
954/1000
1.15
0.3
4555/4150
0.5
90A
24-280
600
1
500
90
150
1145/1200
1.15
0.27
6560/5976
0.5
110A
24-280
600
1
500
110
250
1432/1500
1.15
0.25
10249/9338
0.5
125A
24-280
600
1
500
125
250
1670/1750
1.15
0.22
13950/12709
0.5