English
Language : 

CKRD6010_11 Datasheet, PDF (1/5 Pages) Crydom Inc., – DIN rail mount
CKR60 Series
• Ratings from 10A to 30A @ 660 VAC
• Slim 22.5mm (width) package
• SCR output for heavy industrial loads
• LED input status indicator
• AC or DC control
• Zero-crossing (resistive loads) or random-fire (inductive loads) output
PRODUCT SELECTION
Description
4-32 VDC Control
90-280 VAC Control
18-36 VAC Control
AVAILABLE OPTIONS
10 A
CKRD6010
CKRA6010
CKRA6010E
20 A
CKRD6020
CKRA6020
CKRA6020E
30 A
CKRD6030
CKRA6030
CKRA6030E
OUTPUT SPECIFICATIONS (1)
Description
Operating Voltage (47-63Hz) [VRMS]
Transient Overvoltage [Vpk]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] (2)
Maximum Load Current (3) [Arms]
Minimum Load Current [Arms]
Maximum Surge Current (16.6ms) [Apk]
Maximum On-State Voltage Drop @ Rated Current [Vpk]
Maximum I²t for Fusing (8.3 msec) [A² sec]
Minimum Power Factor (with Maximum Load)
10 A
48-660
1200
1.0
500
10
0.15
120
1.6
60
0.5
20 A
48-660
1200
1.0
500
20
0.15
250
1.6
260
0.5
30 A
48-660
1200
1.0
500
30
0.15
1200
1.6
6000
0.5