C-CT
AC CURRENT SENSORS
˙SPECIFICATIONS
Part Number
C-CT-6
C-CT-10
C-CT-16
C-CT-24
Rated Primary Current
AC 0.1 ʙ 30 A
ʢ50/60 Hzʣ
AC 0.1 ʙ 60 A
ʢ50/60 Hzʣ
AC 0.1 ʙ 100 A
ʢ50/60 Hzʣ
AC 0.1 ʙ 200 A
ʢ50/60 Hzʣ
Max. Input Current
AC 50 Arms
continuous
AC 100 Arms
continuous
AC 200 Arms
continuous
AC 300 Arms
continuous
Output characteristic
AC 100 mV±1 %
AC 200 mV±1 %
AC 333.3 mV±1 %
AC 666.6 mV±1 %
Example
ʢAC30 A RL=10 Ω 50/60 HzʣʢAC60 A RL=10 Ω 50/60 HzʣʢAC100 A RL=10 Ω 50/60 HzʣʢAC200 A RL=10 Ω 50/60 Hzʣ
Phase Accuracy
2.5°±0.5°
ʢAC30 A RL=10 Ω 50 Hzʣ
2.1°±0.5°
ʢAC30 A RL=10 Ω 60 Hzʣ
1.6°±0.5°
ʢAC60 A RL=10 Ω 50 Hzʣ
0.9°±0.5°
0.3°±0.5°
1.3°±0.5°
ʢAC100 A RL=10 Ω 50/60 HzʣʢAC200 A RL=10 Ω 50/60 Hzʣ
ʢAC60 A RL=10 Ω 60 Hzʣ
Hole Diameter
П6 mm
П10 mm
П16 mm
П24 mm
Nominal Current Ratio
3000É¿1
Applicable Frequency
Max. Circuit Voltage
Withstanding Voltage
Insulation Resistance
Open Circuit Protection
Operational Temperature
Storage Temperature
Flame Rating
Output Cable lead
Size and Weight
AWG24
Approx. L=200 mm
19.3×26.4×31 mm
Approx. 20 gs
10 Hzʙ5 kHz
Less than AC600 V
ʢfor insulated cableʣ
AC 2200 V/1 minute
ʢbetween output terminal and outer caseʣ
More than 50 MΩ by 500 V insulation tester
ʢbetween output terminal and outer caseʣ
7.5 VʢZener diodeʣ
-20 ʙ 60 ˆ, less than 80 %RH
Without condensation
-30 ʙ 60 ˆ, less than 80 %RH
Without condensation
UL94 V-0
26.4×25.5×43.3 mm
Approx. 40 gs
AWG22
Approx. L=150 mm
32.5×30.5×46.2 mm
Approx. 75 gs
48.4×35.5×69.6 mm
Approx. 170 gs
˙ PACKAGING SPECIFICATIONS
O#VML1BDLJOHTQFDJGJDBUJPOT
*OEJWJEVBMMZQBDLBHFEJOBQMBTUJDCBH QDQFSCBH 