English
Language : 

JM60030-1MW14 Datasheet, PDF (2/9 Pages) Cooper Bussmann, Inc. – Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks
Technical Data 10192
Effective June 2016
Specifications:
Fuse class
• Class J
Ratings
• Volts: 600 V
• Amps: up to 400 A
• Withstand rating (SCCR): 200 kA Sym RMS
Agency information
• Blocks:
• UL® Listed E14853 – IZLT
• CSA® Certified 47235 — 6225-01
• Covers: UL Listed UL E58836 – JDVS
• RoHS compliant
Poles
• 1-, 2-, 3-pole
Mounting
• 30 and 60 amp blocks DIN-Rail and panel mount
• 100, 200 and 400 amp blocks panel mount only
Flammability ratings
• Blocks: UL 94V0, self-extinguishing
• Covers: UL 94HB, self-extinguishing
Class J ferrule and knifeblade power distribution fuse blocks
Operating and storage temperature range
• Blocks: -40°C to +120°C
• Covers:
• Non-indicating -40°C to +120°C
• Indicating -20°C to +90°C
Materials
• Base: Thermoplastic
• Terminals: Tin-plated aluminum
Conductors
• 75°C/90°C Cu/Al (unless otherwise noted)
Accessories:
• Optional IP20 finger-safe covers in indicating and non-indicating
versions. Order one for each pole.
• Universal marker labels for 30 and 60 amp blocks, Bussmann
series catalog number TM26CB.
• DIN-Rail end stops for blocks rated up to 60 A, Bussmann series
catalog numbers BRKT-ND or BRKT-NDSCRW2.
Recommended fuses (order separately)
Description
Ultimate protection Low-Peak™ LPJ
time-delay fuses
Advanced protection Limitron™ JKS
fast-acting fuses
High speed Class J DFJ drive fuses
Amps
up to 60
70 to 600
up to 60
70 to 600
up to 600
Data sheet no.
1006
1007
1026
1027
1048
Available two-port lineside lug
for easy daisy-chain wiring
configuration. See catalog
number table for applicable
catalog numbers.
Standard phase barriers
for additional safety
Optional see-through, snap-on
cover for easy visual inspection
Tool-less interlocking modular design
for easy point-of-use assembly
Finger grips on cover
for easy removal
Lockout/tagout feature
improves safety
Probe holes for easy testing
without removing cover
Vent slots improve cooling
(no fuse derating necessary)
Optional open fuse indication
speeds troubleshooting
DIN-Rail or panel mounting on each
pole provides installation flexibility
(DIN-Rail mounting applies to 30
and 60 A blocks only)
Multi-port loadside lug
for power distribution to
multiple branch circuit
connections
Ports on power distribution lugs rated
for dual-wire application, increasing the
number of branch circuit connections
(see catalog number table for details)
2
Eaton.com/bussmannseries
Marker label provision
for easy circuit
identification (applies to
30 and 60 A blocks only)