English
Language : 

JCI-3E Datasheet, PDF (2/2 Pages) Cooper Bussmann, Inc. – E-Rated Medium Voltage Fuses for Potential Small Power Trans.
Dimensional Data
A
C
B
Specifications
Buss
Catalog No.
Amps
Maximum
Design Voltage
2400V; E-Rated Fuse; Indicating
JCD-1/2E
.50E
2750V
JCD-1E
1.0E
2750V
JCD-2E
2.0E
2750V
JCD-5E
5.0E
2750V
2400/4800V; E-Rated Fuse; Non-Indicating
JCW-1/2E
.5E
2750V/5500V
JCW-1E
1E
2750V/5500V
JCW-2E
2E
2750V/5500V
JCW-3E
3E
2750V/5500V
JCW-4E
4E
2750V/5500V
JCW-5E
5E
2750V/5500V
5500V; E-Rated Fuse; Non-Indicating
JCE-1/2E
.5E
5500V
JCE-1E
1E
5500V
JCE-2E
2E
5500V
JCE-3E
3E
5500V
JCE-4E
4E
5500V
JCE-5E
5E
5500V
4800V; E-Rated Fuse; Indicating
JCQ-3E
3.0E
5500V
JCQ-5E
5.0E
5500V
JCQ-10E
10.0E
5500V
7200V; E-Rated Fuse; Indicating
JCI-3E
3.0E
8300V
JCI-5E
5.0E
8300V
JCI-10E
10.0E
8300V
14,400V; E-Rated Fuse; Indicating
JCT-3E
3.0E
15500V
JCT-5E
5.0E
15500V
JCT-10E
10.0E
15500V
Fuse clip for 1.6” Diameter Fuses - 1A0835
Fuse clip for 0.81” Diameter Fuses - 1A1837
Dimensions (Inches)
A
B
C
4.5
0.8
0.63
4.5
0.8
0.63
4.5
0.8
0.63
4.5
0.8
0.63
7.31
1.56
1.38
7.31
1.56
1.38
7.31
1.56
1.38
7.31
1.56
1.38
7.31
1.56
1.38
7.31
1.56
1.38
5.6
0.81
0.63
5.6
0.81
0.63
5.6
0.81
0.63
5.6
0.81
0.63
5.6
0.81
0.63
5.6
0.81
0.63
9.44
1.6
1.38
9.44
1.6
1.38
9.44
1.6
1.38
12.88
1.6
1.38
12.88
1.6
1.38
12.88
1.6
1.38
17.5
1.6
1.38
17.5
1.6
1.38
17.5
1.6
1.38
Construction
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Maximum Interrupting Capacity
Amps (Asym.)
Amps (Sym.)
100,000
63,000
63,000
40,000
63,000
40,000
40,000
25,000
60,000
60,000
60,000
60,000
60,000
60,000
40,000
40,000
40,000
40,000
40,000
40,000
60,000
60,000
60,000
60,000
60,000
60,000
50,000
50,000
50,000
50,000
50,000
50,000
130,000
130,000
130,000
80,000
80,000
80,000
130,000
130,000
130,000
80,000
80,000
80,000
130,000
130,000
130,000
80,000
80,000
80,000
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of
this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical informa-
tion that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change design or construction of
any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice,
any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2011 Cooper Bussmann
www.cooperbussmann.com
1211 BU-SB02090
Page 2 of 2
Data Sheet 6002