English
Language : 

EP2M23012GCC Datasheet, PDF (2/2 Pages) Cooper Bussmann, Inc. – Coordination Module
Coordination Module™ Specifications
Voltage
Short-Circuit
Series
Rating
Current Rating
EP2M23012GCC
EP2M23024GCC
EP2M23036GCC
EP2M23042GCC
EP3M23012GCC
EP3M23024GCC
EP3M23036GCC
EP3M23042GCC
EP4M23012GCC
EP4M23024GCC
EP4M23036GCC
EP4M23042GCC
120/208V
120/208V
120/208V
120/208V
120/240V
120/240V
120/240V
120/240V
277/480V
277/480V
277/480V
277/480V
100kA*
100kA*
100kA*
100kA*
100kA*
100kA*
100kA*
100kA*
100kA**
100kA**
100kA**
100kA**
Dimensions – in
WH D
28 36 5.75
28 36 5.75
28 48 5.75
28 48 5.75
28 36 5.75
28 36 5.75
28 48 5.75
28 48 5.75
28 36 5.75
28 36 5.75
28 48 5.75
28 48 5.75
Branch Circuit
Amp Rating
30
30
30
30
30
30
30
30
30
30
30
30
* When protected by upstream LPN-RK 100A max, LPJ 200A max or JJN 200A max, otherwise 10kA.
** When protected by upstream LPS-RK 200A max, LPJ 200A max or JJS 200A max, otherwise 14kA.
Main breaker option may impact selective coordination. Coordination must be verified analyzing time current curves and available current.
Feed-through lugs available upon request. See data sheet 1149 for more information.
Number of
Circuits
12
24
36
42
12
24
36
42
12
24
36
42
Coordination Module™ Catalog Numbering System
EP 2 M 2 30 42 G CC
Prefix
EP = Emergency
Panel
Main
M = MLO
*B =Breaker
Voltage
2 = 120/208V 3P, 4W
3 = 120/240V 1P, 3W
4 = 277/480V 3P, 4W
*Main breaker drops assembly SCCR
to 10kA.
Branch Circuit
Amperage
30A Max
Main Amperage
(200 Amps Max)
Example:
1 = 100A
1.5 = 150A
2 = 200A
Number of
Circuits
12
24
36
42
1
NEMA Type 1 enclosure
with surface mount trim.
2
Ground Bar bolted with set screw
terminations.
3
120/208V or 277/480V Main lugs
with AWG 6-300Kcmil terminations.
6 12 to 42 Circuits.
7
7
Branch circuit breakers
provide circuit isolation.
8 200A Copper main bus.
2
4
Full-Sized neutral bar with set-screw
terminations.
5
Class CC fuse holders with
easyID™ neon indicator
Provides ease of coordination with
superior overcurrent protection and
open fuse indication.
6
Additional main configurations available, see data sheet 1149 for more information.
©2008 Cooper Bussmann
St. Louis, MO 63178
636-394-2877
www.cooperbussmann.com
Reorder # 3115 10-08-5M
Printed in USA
General
Purpose
Enclosure
TYPE 1 only
Type of
Branch Circuit
Fuses
CC Fuses
1
3
4
5
8