CCPLP-1-20G-S Datasheet, PDF (2/6 Pages) Cooper Bussmann, Inc. – Low Profile Compact Circuit Protector (CCPLP)
Technical Data 10372
Effective December 2015
Low Profile Compact Circuit Protector (CCPLP)
UL Class G, CC, midget and IEC 10x38mm fused disconnect switches
Catalog symbol:
• CCPLP-(poles)-(amps)-(terminal)
Description:
The revolutionary Bussmann® series Low Profile Compact Circuit
Protector (CCPLP) fused disconnect switch is available in 1-, 2-
and 3-pole versions for UL® Class CC (1/10-30A), Class G (20A),
13/32”x1-1/2” midget UL (1/10-30A) and IEC 10x38 aM/gG
(0.16-32A) fuses.
The CCPLP has the smallest footprint of any UL 98 Listed fused
disconnect switch along with up to a 200kA SCCR to help
improve equipment SCCR.
Class CC and G versions are easily selectively coordinated with
the upstream Bussmann series CUBEFuse™ using published
fuse ampacity ratio tables.
Unique panel mounting permits easy integration into many
panel designs and provides a high SCCR alternative to low
profile circuit breakers on the market.
Specifications:
Ratings
• Frequency
• 50/60Hz
• Impulse voltage
• 8kV
• Volts
• 600Vac (Class CC up to 30A, Class G 20A)
• 550Vac (10x38 IEC Class aM 0.16-16A)
• 500Vac (10x38 IEC Class gG 0.5-25A)
• 400Vac (10x38 IEC Class aM 20-32A, gG 32A)
• 240Vac (13/32” x 1-1/2” midget UL 30A)
• Amps
• Up to 30A (UL)
• Up to 32A (IEC)
• SCCR
• 200kA (Class CC)
• 120kA (10x38 IEC Class gG and aM)
• 100kA (Class G)
• 10kA (13/32”x1-1/2” midget UL)
Poles
• 1-, 2- and 3-pole factory configured
• 2- and 3-pole versions feature ganged switches and
phase barriers.
Agency information
• Finger-safe IP20 from panel front
• CE compliant
• RoHS compliant
• For Class G fuse versions
• UL 98 Listed, File E302370, Guide WHTY
• IEC® 60947-3 AC-23A
• For Class CC fuse versions
• UL 98 Listed, File E302370, Guide WHTY
• cULus to CSA Standard 22.2 No. 4-04, File E302370,
Guide WHTY7
• IEC 60947-3 AC-23A
• For UL midget and 10x38 IEC fuse versions
• UL 508 Listed, File E320230, Guide NRNT
• cULus Listed to CSA 22.2 No. 14-05, File E320230,
Guide NRNT7
• IEC 60947-3 AC-23A
Terminals and conductors 75°C/90°C Cu
• Screw terminal - #10-32 phil-slot screw with external tooth
lock washer — use with properly rated/UL Listed ring or fork
terminal
• Pressure plate terminal - #10-32 phil-slot screw — single
22-6AWG solid or stranded
Terminal screw torque
• 20 Lb-In (2.2 N•m)
Mounting
• Front panel mounting with customer supplied M3 screws
• Mounting screw torque 4-5 Lb-In (0.4-0.5 N•m)
Open fuse indication*
• Local open fuse indication provided by a orange neon lamp
on each pole, minimum voltage 90Vac
* Open fuse indication requires an energized, closed circuit with an open
fuse in the CCPLP and the switch in the ON position.
Ambient storage and operating temperature
• -20°C to 90°C, 85% relative humidity non-condensing
Flammability rating
• UL 94 V2
Lockout/tagout provisions
• Brady pin-out device, P/N 90844
Circuit labeling provisions
• Accepts up to two universal marker labels (P/N TM26CB)
Carton quantity
• 12 poles (1-pole: 12 units, 2-pole: 6 units, 3-pole: 4 units)
Minimumn enclosure size
• 6”x6”x4” per UL 98 Listing