English
Language : 

10-315A Datasheet, PDF (2/2 Pages) Cooper Bussmann, Inc. – Square Body – DIN 43 620
Square Body – DIN 43 620
690V (IEC/U.L.) 10-315A
Bussmann®
®
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other volt-
ages, the clearing I2t is found by multi-
plying by correction factor, K , given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL, which may appear across the fuse
during its operation as a function of the
applied working voltage, Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current . The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current .
1.5
K
1.0
0.5
0.4
0.3
0.2
Eg
100 200 300 400 500 600 690
1.4
1.2 UL
103
9
8
7
6
5
4
Eg
3
200 300 400 500 600 690
1.0
0.8
Kp
0.6
0.5
0.4
0.3
0.2
0.1
Ib
30 40 50 60 70 80 90 100%
Dimensions
DIN 43 620: Type DIN 000
Dimension in mm.
1mm = 0.0394∑ 1∑ = 25.4mm
48
21
35
54 Max
79
Indicator
15
6
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled.
This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right,
without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
7-11-01
SB01191
Form No.
Page 2 of 2
BIF Doc #720016