English
Language : 

2NCLPT-1E Datasheet, PDF (10/72 Pages) Cooper Bussmann, Inc. – PT Medium voltage fuses for potential and small power transformers
Technical Data 6002
Effective March 2016
PT medium voltage fuses for potential and
small power transformers
5.5kV maximum system voltage
Dimensions - in (mm)
Amp rating Length A
0.5 5.6 (142)
0.5 5.6 (142)
0.5 7.4 (188)
0.5 9.5 (241)
1 5.6 (142)
1 5.6 (142)
1 7.4 (188)
1 9.5 (241)
1.5 9.5 (241)
2 5.6 (142)
2 5.6 (142)
2 7.4 (188)
3 5.6 (142)
3 5.6 (142)
3 9.5 (241)
3 7.4 (188)
4 5.6 (142)
4 7.3 (185)
5 9.5 (241)
5 5.6 (142)
5 5.6 (142)
5 7.3 (185)
10 9.5 (241)
15 7.4 (188)
Diameter B Clip centers C
0.8 (20) 4.8 (122)
1 (25) 4.4 (112)
1.6 (41) 6.2 (157)
1.6 (41) 8.1 (206)
1 (25) 4.4 (112)
0.8 (20) 4.8 (122)
1.6 (41) 6.2 (157)
1.6 (41) 8.1 (206)
1.6 (41) 8.1 (206)
1 (25) 4.4 (112)
0.8 (20) 4.8 (122)
1.6 (41) 6.2 (157)
1 (25) 4.4 (112)
0.8 (20) 4.8 (122)
1.6 (41) 8.1 (206)
1.6 (41) 6.2 (157)
0.8 (20) 4.8 (122)
1.6 (41) 5.9 (150)
1.6 (41) 8.1 (206)
1 (25) 4.4 (112)
0.8 (20) 4.8 (122)
1.6 (41) 5.9 (150)
1.6 (41) 8.1 (206)
1.6 (41) 6.2 (157)
Catalog No. (Interrupting rating - kA)
Indicating
Non-indicating
— 5.5AMWNA0.5E (50)
— 5.5ABWNA0.5E (50)
5.5CAVH0.5E (63)
JCW-1/2E (40)
5CLPT-.5E (80)† 5NCLPT-.5E-A (63)
— 5.5ABWNA1E (50)
— 5.5AMWNA1.0E (50)
5.5CAVH1E (63)
JCW-1E (40)
5CLPT-1E (80)†
5NCLPT-1E-A (63)
5CLPT-1.5E (80)†
—
— 5.5ABWNA2E (50)
— 5.5AMWNA2.0E (50)
5.5CAVH2E (63)
JCW-2E (40)
— 5.5ABWNA3E (50)
— 5.5AMWNA3.0E (50)
5CLPT-3E (80)
—
JCW-3E (40)
— 5.5AMWNA4.0E (50)
—
JCW-4E (40)
5CLPT-5E (80)
—
— 5.5ABWNA5E (50)
— 5.5AMWNA5.0E (50)
—
JCW-5E (40)
5CLPT-10E (80)
—
—
5.5CAV15E (63)
† Does not comply with ANSI C37.46 for “E” rating.
CLPT Type mountings and hardware 5.5kV maximum (4.8kV nominal)*
Recommended fuseclip
1A1837
A3354705
1A0835
A3354705
1A1837
1A0835
1A0835
A3354705
1A1837
1A0835
A3354705
1A1837
1A0835
1A0835
1A1837
1A0835
1A0835
A3354705
1A1837
1A0835
1A0835
Fuse mounting
Amp rating type**
CLPT and NCLPT-A Mounting
0.5–10
Non-disconnect
Disconnect†
Catalog number
BIL
Mounting (including live parts, end fittings)***
Live parts (including End fittings
(kV) Porcelain insulator
Glass-polyester insulator end fittings)***
(disconnect only)
60 5CLPT-PNM-A
60 5CLPT-PDM-A
5CLPT-GNM-A
5CLPT-GDM-A
CLPT-NL
CLPT-DL
—
CLPT-DF
* Refers to 5CLPT and 5NCLPT-A fuses only.
** See page 70 for dimensions and diagrams of typical mounting.
*** End fittings supplied only when required.
† Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
10
Eaton.com/bussmannseries