English
Language : 

TPM-3 Datasheet, PDF (1/4 Pages) Cooper Bussmann, Inc. – Telpower® Miniature Fused Disconnect Switch
Telpower® DC Power Protection Systems
Telpower® Miniature Fused Disconnect Switch
Bussmann®
TPM & TPMDS
TPM & TPMDS
TPMDS - Telpower® Miniature Fused Disconnect Switch
TPM - Telpower® Miniature Fuse - Current Limiting
Ampere Ratings: 3-30A
Voltage Rating: 80VDC
Interrupting Rating: 20,000A
Agency Information:
UL Recognized (investigated to UL 1801) as a
disconnect switch for the interruption of load current
by means of withdrawing the fuse pullout.
Recognized to U.S. and Canadian requirements under the
component recognition program of Underwriters
Laboratories Inc.
Files E219046 and E56412.
Catalog Number
TPM-3
TPM-4
TPM-5
TPM-6
TPM-7
TPM-8
TPM-10
TPM-12
TPM-15
TPM-20
TPM-25
TPM-30
TPMDS-E
TPMDS-M
Description
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Fuse
Miniature Disconnect, English
Miniature Disconnect, Metric
Ampere Rating
3A
4A
5A
6A
7A
8A
10A
12A
15A
20A
25A
30A
3-30A
3-30A
General Information:
• Smallest and most versatile fused disconnect
switch available.
• Small size allows for assembly into 1 U (1.75 inch /
44.5 mm) panel.
• AmpColor ID™ System for easy fuse replacement.
• Switch design provides for easy panel mounting by single
captive 4-40 (M3) nut and panel notch integral to switch
footprint.
• Local and remote open fuse indication. Local alarm
indication provided by LED on TPM fuse.
• Current-limiting capability
• Complete system coordination capability
• Load connection: 1/4 inch quick-connect or bolted
connection with 10-32 (M5) captive nut.
• Line connection: 1/4 inch quick-connect or screw
connection with clearance hole for #10 (M5) bolt.
• Maximum alarm circuit current: 20 mA
• Materials:
Fuse housing - black thermoplastic, UL 94 V-0, 170ºC RTI
Switch housing - black thermoplastic, UL 94 V-0, 140ºC RTI
CE logo denotes compliance with European Union Low
Voltage Directive (50-1000VAC, 75-1500VDC). Refer
to Data Sheet: 8002 or contact Bussmann Application
Engineering at 636-527-1270 for more information.
TPM Alarm Schematic
NOTES:
1. The resistance, R, must be provided by the end-user
to limit the alarm output current to a maximum of
20 mA. The value, R, should be calculated using the
system voltage value.
• If remote alarm functionality is not required,
the END-USER CIRCUITRY must still be supplied
to provide a resistive path to the return for the
local alarm to properly function.
2. The fuse is polarized to maintain proper orientation with
the switch housing. The line and load terminals are
identified on the switch housing.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are definition uncontrolled. This bulletin
is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information contained
in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
11-13-02
SB02302
Look for Telpower® BLUE™ fuses exclusively from Cooper Bussmann.
Form No. TPM & TPMDS
Page 1 of 4
Data Sheet: 5022