English
Language : 

SPP40SP1120SN Datasheet, PDF (1/3 Pages) Cooper Bussmann, Inc. – SURGE PROTECTION MADE SIMPLE™ FOR LIGHT COMMERCIAL & RESIDENTIAL APPLICATIONS
SURGE PROTECTION MADE SIMPLE™ FOR LIGHT COMMERCIAL & RESIDENTIAL APPLICATIONS
SURGEPOD™ PRO SPD FOR UL 1449 3rd Edition Listed Loadside and Lineside Protection
Description
The Cooper Bussmann SurgePOD™ PRO is a Type 1 UL
Listed 1449 3rd Edition surge protective device suitable for
installation on both the loadside or lineside of the service
entrance overcurrent protective device.
Available in popular voltage and system specific versions to
match common residential and light commercial electrical
system and equipment requirements. The SurgePOD PRO
delivers superior surge protection using MOV thermal
disconnect technology that eliminates the need for additional
overcurrent protection.
Parallel connection to the electrical system permits the
SurgePOD PRO SPD to be installed on any ampacity panel.
• Type 1 UL 1449 3rd Edition Listed SPDs are easily selected
and installed on the loadside or lineside of the service
entrance overcurrent protective device
• Voltage specific models precisely match and protect
electrical systems and equipment better than
“one-size-fits-all” SPDs
• Thermal disconnect technology eliminates the need for
additional fusing
• Compact UV resistant NEMA 4X enclosure for indoor or
outdoor applications
• easyID™ LED status indicator provides surge protection
status at a glance
Dimensions - in
1-1/16” Dia.
3-3/8”
1-11/16”
1-11/16”
2-1/16” 2-1/16”
4-1/8”
3-3/16”
4-1/16”
7/8”
easyID™ LED
Status Indicator
SPP40SP1120SN
SPP40SP2240PN
SPP40SP3240DLG SPP40SP3208WYG
SPP40SP3480DLG SPP40SP3480WYG
NEMA 4X Rated Pro
Type 1 UL Listed SPD
Type 1 SPD Part Number System
SPP 40S PX XXX XXX
SPP = Product Series
Surge Protection PRO
Surge Rating
40S = 40kA max discharge current
No of Wires/Poles
P1 = 1 P2 = 2 P3 = 3 P4 = 4
Rated System Voltage
120, 208, 240, 480Vac
System
SN = Single-Phase 2 Wire, 2 Connection Points
PN = Split-Phase, 3 Wire, 3 Connection Points
DLG = Three-Phase Delta 3 Wire + G, 4 Connection Points
WYG = Three-Phase Wye 3 Wire, 4 Connection Points
www.cooperbussmann.com/Surge
0213 BU-SB13071
Page 1 of 3
Data Sheet 10033