English
Language : 

SPH50SP1120SN Datasheet, PDF (1/4 Pages) Cooper Bussmann, Inc. – SURGE PROTECTION MADE SIMPLE™ FOR COMMERCIAL & INDUSTRIAL APPLICATIONS
SURGE PROTECTION MADE SIMPLE™ FOR COMMERCIAL & INDUSTRIAL APPLICATIONS
SURGEPOD™ HEAVY DUTY SPD FOR UL 1449 3rd Edition Listed Loadside and Lineside Protection
SPD Type 2
Description
The Cooper Bussmann SurgePOD™ HEAVY DUTY is a Type 1
UL Listed 1449 3rd Edition surge protective device suitable for
installation on both the loadside or lineside of the service
entrance overcurrent protective device.
Available in voltage and system specific versions to match
electrical system and equipment requirements. The SurgePOD
HEAVY DUTY delivers optimum surge protection using
advanced patent pending SurgePOD™ module featuring
thermal disconnect technology that eliminates the need for
additional overcurrent protection.
easyID™ LED
Status Indicator
Parallel connection to the electrical system permits the
SurgePOD HEAVY DUTY SPD to be installed on any ampacity
panel.
• Type 1 UL 1449 3rd Edition Listed SPDs are easily selected
and installed on the loadside or lineside of the service
entrance overcurrent protective device
• Patented Cooper Bussmann SurgePOD module technology
eliminates the need for additional fusing
• Voltage specific models precisely match and protect
electrical systems and equipment up to 600Vac
• Compact UV resistant NEMA 4X for indoor or outdoor
applications
• easyID™ LED status indicator provides surge protection
status at a glance
SPH50SP1120SN
SPH50SP1240SN
SPH50SP1347SN
SPH50SP2120SNG
SPH50SP2240SNG
SPH50SP2347SNG
SPH50SP2240PN
SPH50SP2480PN
SPH50SP3240PNG
SPH50SP3480PNG
SPH50SP3240DLG
SPH50SP3480DLG
SPH50SP4240HLG
SPH50SP4480HLG
SPH50SP3208WYG
SPH50SP3480WYG
SPH50SP3600WYG
SPH50SP4208WYNG
SPH50SP4480WYNG
SPH50SP4600WYNG
NEMA 4X Rated Heavy Duty
Type 1 UL Listed SPD
Dimensions - in
3-3/8”
1-1/16” Dia.
1-11/16”
1-11/16”
2-1/16” 2-1/16”
4-1/8”
3-3/16”
4-1/16”
7/8”
Type 1 SPD Part Number System
SPH 50S PX XXX XXX
SPH = Product Series
Surge Protection Heavy Duty
Surge Rating
50S = 50kA max discharge current
No of Wires/Poles
P1 = 1 P2 = 2 P3 = 3 P4 = 4
Rated System Voltage
120, 208, 240, 347, 480, 600Vac
System
SN = Single-Phase 2 Wire, 2 Connection Points
SNG = Single-Phase 2 Wire + G, 3 Connection Points
PN = Split-Phase 3 Wire , 3 Connection Points
PNG = Split-Phase 3 Wire + G, 4 Connection Points
DLG = Three-Phase Delta 3 Wire + G, 4 Connection Points
HLG = Three-Phase Highleg Delta 4 Wire + G, 5 Connection Points
WYG = Three-Phase Wye 3 Wire, 4 Connection Points
WYNG = Three-Phase Wye 3 Wire + G, 5 Connection Points
www.cooperbussmann.com/Surge
0213 BU-SB13145
Page 1 of 4
Data Sheet 2163