English
Language : 

SC-1 Datasheet, PDF (1/3 Pages) Cooper Bussmann, Inc. – SC Class G, 600Vac/480Vac, 1⁄2-60A
Technical Data 1024
Effective December 2015
Supersedes August 2013
BUSSMANN
SERIES
SC Class G, 600Vac/480Vac, 1⁄2-60A
size-rejecting fuses
Catalog numbers (amps)
SC-1⁄2
SC-6
SC-1
SC-7
SC-1-1⁄2
SC-8
SC-2
SC-10
SC-2-1⁄2
SC-12
SC-3
SC-15
SC-4
SC-20
SC-5
SC-25
SC-30
SC-35
SC-40
SC-45
SC-50
SC-60
Carton quantity:
Amp rating
1/2-20
25–60
Carton qty.
4
2
Catalog symbol:
• SC-(amp)
Description:
Basic protection Class G size-rejecting, current
limiting fuses. 1/2 to 6A Fast-acting, 7 to 60A
time-delay. Time-delay – 12 seconds (minimum)
at 200% of rated current.
Specifications:
Ratings
• Volts
• 600Vac/170Vdc (½-20A)
• 480Vac/300Vdc (25-60A)
• Amps 1/2-60A
• IR
• 100kA Vac RMS Sym.
• 10kA Vdc
Agency information
• UL® Listed, Std. 248-5, Class G,
Guide JDDZ, File E4273
• CSA® Certified, C22.2 No. 248.5,
Class 1422-01, File 53787
• CE
• RoHS compliant
Dimensions - in (mm):
A
(Length)
0.41”
(10.41mm)
Amp rating
1/2-15
20
25 to 30
35 to 60
A
1.31 (33.3)
1.41 (35.8)
1.62 (41.1)
2.25 (57.1)
Features:
• Meets basic protection requirements of
NEC®, Canadian Electrical Code (CEC), UL
and CSA.
• Most economical overcurrent protection
solution compared to circuit breakers.
• For use in various non-demanding, general
purpose applications.
• Compact branch-circuit units with high
interrupting rating and current-limitation.
• With up to a 600V rating, they can be used in
120/208V, 120/240V, and 277/480V circuits.
• Size rejection by length helps prevent
overfusing.
• Fuses 7 amps and above have a degree of
overload time-delay that permits them to
pass temporary overloads.