English
Language : 

S505-2-R Datasheet, PDF (1/2 Pages) Cooper Bussmann, Inc. – 5 x 20mm Time-Delay, Ceramic Tube Fuses
5 x 20mm Time-Delay, Ceramic Tube Fuses
S505 Series
HALOGEN
HF
FREE
5 x 20mm fuse with
optional axial leads
Dimensions - mm
• Ratings above 6.3A have a maximum
0.81mm diameter lead
• With TR2 packaging code, leadwire
length is 19.05mm
Pb
Description
• Time-delay, high breaking capacity
• Available with optional axial leads
• Ceramic tube, silver-plated endcap construction (500mA-800mA),
nickel-plated brass endcap construction (1-12A)
• Optional sleeve is flexible flouropolymer (UL flammability rating VW-1).
Consult factory for details.
• 5 x 20mm physical size
• Designed to IEC 60127-2 (500mA-10A) & extension 12A
Electrical Characteristics
Amps
1.5In 2.1In
2.75In
Min Max Min Max
min. min. ms s
4In
Min Max
ms s
10In
Min Max
ms ms
<1A
60
1A-3.15A 60
4A-6.3A 60
8A-12A 30
30 250 80s 50 5s
30 750 80s 95 5s
30 750 80s 150 5s
30 750 80s 150 5s
5 150
10 150
10 150
10 150
Specifications
Agency Information
• UL Recognized Card: Guide JDYX2, File E19180, JDYX8, File E19180
• CSA Component Acceptance: File 53787
• SEMKO: File 816547, 1119019
• VDE: File 40014091, 40024352, 40023140
• BSI: File KM55676
• IMQ: File CA03.00100 and CA03.00529
• PES+JET: File 1641-31003-1009, 1641-31003-1010,
1641-31003-1011, 1641-31003-1012, 1641-31003-2001,
1641-31003-2002
• CCC: File 2002010207011295, CQC11012061930
• KC-Mark: File SU05011-4012A, SU05011-5004A
Ordering
• Specify packaging code (insert packaging code prefix before part number)
e.g., BK- (or BK1-/TR2-) S505-1-R
• Specify option codes if desired (for axial leads, insert “V” between catalog
series and amp rating) e.g., BK-S505-V-1-R
Voltage Interrupting Typical DC Cold Typical
Typical
Agency Information
Product
Rating Rating at Rated Resistance Pre-arching Voltage
CCC/ PSE/
Code
AC Voltage (50Hz) AC1
(Ω)2
I2t (A2s)AC3 Drop (mV)4 IMQ5 VDE SEMKO cURus CQC5 JET CSA5 KC5 BSI
S505-500-R 250
1500
0.5070
0.188X
295
XX X
XX
X
X
S505-800-R 250
1500
0.2370
0.632X
189
XX X
XX
X
X
S505-1-R
250
1500
0.1401
1.28
152.5
XX X
X XXXXX
S505-1.25-R 250
1500
0.1075
2.22
150
XX X
X XXXXX
S505-1.6-R 250
1500
0.0700
6.78
125
XX X
X XXXXX
S505-2-R
250
1500
0.0545
9.60
118.5
XX X
X XXXXX
S505-2.5-R 250
1500
0.0395
16.60
115
XX X
X XXXXX
S505-3.15-R 250
1500
0.0305
36.60
102.5
XX X
X XXXXX
S505-4-R
250
1500
0.0185
38.45X
86.5
XX X
X XXXXX
S505-5-R
250
1500
0.0131
71.30X
77.5
XX X
X XXXXX
S505-6.3-R 250
1500
0.0102
111X
75
XX X
X XXXXX
S505-8-R
250
1500
0.0077
228X
73
XX X
X X6 X X X X
S505-10-R 250
1500
0.0061
397
72
XX X
X X6 X X X X
S505-12-R 250
1000
0.0053
713.7X
77
X
X
1. Interrupting ratings: 500mA to 10A were measured at 70% to 80% PF on AC,12A was measured
at 100% PF on AC.
2. Typical DC Cold Resistance (measured at <10% of rated current).
3. Typical Pre-Arching I2t (measured at listed interrupting rating and rated voltage if not specified);
With "X" specified, the typical I2t value is measured at 10 times of rated current under DC.
4. Typical Voltage Drop( Voltage Drop was measured at 20°C ambient temperature at rated current).
5. No room for "CSA" & "KC" on the fuse endcap for Non-V Rev. No room for "IMQ", "CQC' or "KC"
on fuse endcap for -V Rev.
6. CQC only.
1111 BU-SB11758
Page 1 of 2
Data Sheet 2037