English
Language : 

KRP-C-601SP Datasheet, PDF (1/4 Pages) Cooper Bussmann, Inc. – Low-Peak™ KRP-C Class L 600Vac/300Vdc, 601-2000A, time-delay fuses
Technical Data 1008
Effective February 2016
Supersedes August 2015
Low-Peak™ KRP-C Class L 600Vac/300Vdc,
601-2000A, time-delay fuses
Catalog symbol:
• KRP-C-(amp)SP
Description:
Bussmann® series Ultimate protection KRP-C
Class L current-limiting, time-delay fuses. Time-
delay – 4 seconds (minimum) at 500% of rated
current.
Specifications:
Ratings
• Volts
• 600Vac
• 300Vdc
• Amps 601-2000A*
• IR
• 300kA Vac RMS Sym.
• 100kA Vdc
* Use KRP-CL fuses for ratings from 225 to 600 amps.
Agency information
• UL® Listed, Guide JDDZ, File E4273
• CSA® Certified, Class 1422-02, File 53787,
Class L per CSA C22.2, No. 248.10
• CE
• RoHS compliant
Catalog numbers (amps)
KRP-C-601SP KRP-C-900SP
KRP-C-650SP
KRP-C-700SP
KRP-C-750SP
KRP-C-800SP
KRP-C-801SP
KRP-C-1000SP
KRP-C-1100SP
KRP-C-1200SP
KRP-C-1350SP
KRP-C-1400SP
Carton quantity:
KRP-C-1500SP
KRP-C-1600SP
KRP-C-1800SP
KRP-C-1900SP
KRP-C-2000SP
Amp rating
601-2000
Carton qty.
1
Dimensions - in:
All other tolerances (± 0.02)
All Slots and Holes
0.63" (±0.03)
8.63"
(± 0.09)
6.75"
10.75"
(± 0.09)
601
to
800A
801
5.75" to
1200A
1350
to
1600A
1800
to 3.75"
2000A
0.38"
0.38" 0.44" 0.5"
2"
2.5"
2.53"
Max.
Features:
2"
2.5"
2.78"
Max.
2.38"
3"
3.03"
Max.
2.75"
3.5"
3.53"
Max.
Terminal:
Width (± 0.06)
Thickness (± 0.03)
• Industry’s only UL Listed and CSA Certified
fuse with a 300kA interrupting rating that allows
for simple, worry-free installation in virtually any
application.
• Fast short-circuit protection with time-delay
performance provide ultimate protection.
• Consistent 2:1 ampacity ratios for all Low-Peak
fuses make selective coordination easy.
• Time-delay for close sizing load.
• Current-limiting action of the fuse generally affords
considerable reduction in bus bracing.
• All-purpose silver-linked fuse for both overload and
short-circuit protetion for high capacity systems
(mains and large feeders).
• O-ring seals maximize pressure build-up during
current-limiting action and ensure filter retention.
• High-grade silica sand filler accelerates response
of fuse to short-circuits by having quenching effect
on the fuse arc.
• 99.9% pure silver links provide low watt loss with
low operating temperature on normal current
levels and minimizes total clearing I2t fault
energy left-through.