JKS-1 Datasheet, PDF (1/3 Pages) Cooper Bussmann, Inc. – JKS — 600Vac, 1-60A, Fast-Acting Fuses | |||
|
LIMITRON⢠Class J
JKS â 600Vac, 1-60A, Fast-Acting Fuses
Dimensions - in
Description: Advanced protection Class J curent-limiting,
fast-acting fuses.
Catalog Symbol: JKS-(amp)
Ratings:
Volts â 600Vac
Amps â 1-60A
IR â 200kA Vac RMS Sym.
Agency Information:
CE, UL Listed, Std. 248-8, Class J, Guide JDDZ, File E4273
CSA Certified, C22.2 No. 248.8, Class 1422-02, File 53787
Catalog Numbers (amps)
JKS-1
JKS-8
JKS-2
JKS-10
JKS-3
JKS-12
JKS-4
JKS-15
JKS-5
JKS-20
JKS-6
JKS-25
JKS-30
JKS-35
JKS-40
JKS-45
JKS-50
JKS-60
Carton Quantity:
Amp Rating
1â60
Carton Qty.
10
2.25"
(±0.03)
0.5"
0.81"
(±0.03)
1 to 30A
2.38"
(±0.03)
1.06"
0.63" (±0.03)
35 to 60A
Features:
⢠Provides 10X better current limitation to help prevent
equipment damage caused by short-circuit events.
⢠200kA Interrupting rating complies with NEC® Section 110.9
for today's large capacity systems.
⢠Fast-acting fuse helps prevent equipment damage caused
by short-circuit events.
⢠Ideal for critical industrial or commercial applications that
have specific current limitation requirements.
Recommended Fuse Blocks and Holders
Fuse Amps
1-Pole
2-Pole
Open Blocks
0-30
J60030-1_
J60030-2_
35-60
J60060-1_
J60060-2_
âPyramidâ Blocks
0-30
â
â
CH Series Holders
0-30
CH30J1_
CH30J2_
35-60
CH60J1_
CH60J2_
Safety J⢠Holders
0-30
JT60030_
â
35-60
JT60060_
â
3-Pole
J60030-3_
J60060-3_
JP60030-3_
CH30J3_
CH60J3_
â
â
For additional information on the Class J fuse blocks and
holders, see data sheets # 1114 (open blocks), #1108
(pyramid blocks), # 2144 (CH Series) and # 1152 (Safety J).
Fuse Reducers For Class J Fuses
Equipment
Fuse Clips
60A
100A
200A
Desired Fuse
(Case) Size
30A
30A
60A
60A
â Not for bolt-in applications.
Catalog Numbers
(Pairs)
J-63
J-13
J-16
J-26â
0813
BU-SB13735
Page 1 of 3
Data Sheet # 1026
|
▷ |