English
Language : 

HPF-C Datasheet, PDF (1/1 Pages) Cooper Bussmann, Inc. – Panel-Mount Fuseholder with Screw-type Knob For Úܽ£ª· Å 1Þ½Á¤· to 1Ú½ª· Fuses
Bussmann®
Panel-Mount Fuseholder with Screw-type Knob HPF
For ⁄‹Ω£™∑ ≈ 1fiΩ¡§∑ to 1⁄Ω™∑ Fuses
Series
Dimensional Data All dimensions (ؓ0.015)
Catalog Symbol: HPF, HPF-C, HPF-L, HPF-EE, HPF-JJ,
HPF-FF, HPF-RR, and HPF-WT
Panel-Mount
Agency Information:
UL Recognized, Guide IZLT2, File E14853
CSA Certified, Class 6225-01, File 47235
Flammability Rating: UL 94 HB
Electrical Ratings
Catalog
Symbol
HPF
HPF-C
Amps
30(3)
30(4)
Volts
AC
600
600(4)
Fuse Description
1⁄Ω™∑ (38.1mm).
1⁄Ω™∑ (38.1mm) clear knob.
HPF-L
5
600
BBS,⁄‹Ω£™∑ ≈ 1‹Ω•∑ fuses.
HPF-EE
15
600
SC 0-15, ⁄‹Ω£™∑ ≈ 1fiΩ¡§∑ fuses.
HPF-JJ
20
600
SC 20, ⁄‹Ω£™∑ ≈ 1⁄‹Ω£™∑ fuses.
HPF-FF(2)
30(3)
480
SC 25 & 30, ⁄‹Ω£™∑ ≈ 1fiΩ•∑ fuses.
HPF-RR
30(3)
600
KTK-R, LP-CC & FNQ-R Class CC fuses.
HPF-WT
30(3)
600
Splash-proof knob.
(2)No CSA Certification
(3)20A max. when used with quick connect terminals.
(4)HPF-C ratings for CSA - 15A, 250V.
With Fuse
2.81" Max.
(71.4mm)
SE F
1.00" 1.31" 1.78"
(25.4mm) (33.3mm) (45.2mm)
.250" ± .003"
(6.35 ± .08mm)
(Typ. 2)
1.125"
(28.6mm)
0.180" DIA.
(4.6mm)
0.88"
(22.2mm)
2.69" Max.
(68.3mm)
Without Fuse
Mounting Hole
Flange Rear of Panel
Mounting Hole
Flange Front of Panel
1.031" + 0.003"
(26.2mm + 0.08mm)
0.187" + 0.002"
(4.75mm + 0.05mm)
1.312" + 0.003"
(33.3mm + 0.08mm)
0.890" + 0.003"
(22.6mm + 0.08mm)
1.312" + 0.003"
(33.3mm + 0.08mm)
Maximum panel thickness, mounting flange in front of panel
Assumes Pollution Degree 3 per UL 840:
Conductive pollution, or dry, nonconductive pollution that
becomes conductive due to condensation that is expected.
Maximum panel thickness not including any sealing gaskets.
System Voltage 600V
480
277
240
120
Fuseholder
mm Inches mm Inches mm Inches mm Inches mm Inches
HPF
0.61 1/32” 1.50 1/32” 5.77 7/32” 6.32 7/32” 7.80 9/32”
Thicker panels may be used if fuse holder load terminal is fully insulated, using a
UL recognized (VW-1) insulative heat-shrink tubing, or if anticipated environment
is of Pollution Degree 1 or 2, or if panel is nonconductive.
Pollution Degree 2- Normally, only nonconductive pollution. However, a temporary
conductivity caused by condensation may be expected.
Pollution Degree 1- No pollution or only dry, nonconductive pollution.
The pollution has no influence.
Maximum panel thickness, mounting flange behind the panel:
5.08mm/0.200” (flush to knob collar)
CE logo denotes compliance with European Union Low Voltage Directive
(50-1000Vac, 75-1500Vdc). Refer to Data Sheet: 8002 or contact
Bussmann Application Engineering at 636-527-1270 for more information.
General Information:
• Screw-type knob.
• One-piece side terminal and threaded insert eliminates two-
piece solder fabrication.
• Combination ⁄Ω¢∑ quick-connect/solder terminals for
versatility.
• The HPF series functionally replaces the Buss® HPC series.
• Replacement knob-BK/9789-⁄Ω™ (for HPF, HPF-L, HPF-EE,
HPF-JJ, HPF-FF and HPF-RR).
• The HPF-EE, -RR, -FF, and -JJ are UL
Recognized for branch circuit protection.
• Do not put tension on line (rear) terminal.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without notice, any technical information con-
tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
6-3-04
SB04184
Form No. HPF Series
Page 1 of 1
Data Sheet: 2114