HEX Datasheet, PDF (1/2 Pages) Cooper Bussmann, Inc. – TRON® In-Line Fuseholders | |||
|
TRON® In-Line Fuseholders
Double-Pole for Class CC and ââ¹â¦Â£â¢â â 1ââ¦â¢â Fuses
Bussmann®
HEX & HEY
Series
Catalog and Specification Data
Conductor Terminals
Conductor Data
Terminal Type
Size
Catalog
Symbol
HEX Series
Catalog Symbol: HEX-AA(1) (2), HEX-AB, HEX-AC, HEX-AD,
HEX-AE, HEX-AY, HEX-BB, HEX-CC, HEX-JJ, HEX-JK, and
HEX-KK.
In-Line Fuseholders, Double Pole
Water-Resistant
For breakaway holders, see page 2
Agency Information:
(1)UL Recognized, Guide IZLT2, File E14853
(2)CSA Certified, Class 6225-01, File 47235
HEX â For any ââ¹â¦Â£â¢â â 1ââ¦â¢â fuse. Fuseholder rated 30A,
600V (CSA Listed 15A max.). Typical fuse types: BAF,
FNM, FNQ, and KTK (ââ¦Â¡Âº - 30A).
Copper Crimp
Copper Set-Screw
#12 to #8
#12
#10
#6
#4
#8
#4
#6
#2
#4
1
â¢
â¢
A
2
â¢
â¢
2
â¢
â¢
1
â¢
â¢
B
1
â¢
â¢
2
â¢
â¢
C
1
â
â¢
2
â¢
â¢
D
1
â
â¢
2
â¢
â¢
E
#12 to #3
1
â¢
â¢
J
Aluminum Set-Screw
#12 to #3
#12 to #2
2
â¢
1
â¢
â¢
K
â¢
L
HEY Series
Catalog Symbol: HEY-AA, HEY-AB,
HEY-AC, HEY-AD, HEY-AE, HEY-AL, HEY-BB, and HEY-JJ.
In-Line Fuseholders, Double-Pole
Water-Resistant
For breakaway holders, see page 2
HEY â Optional breakaway receptacle, water-resistant,
polarized, and accepting Class CC branch circuit fuses (Buss
Type KTK-R, FNQ-R, & LP-CC; 600V or less, 200,000A inter-
rupting rating.) Particularly applicable in street lighting circuits.
Example:
A double-pole, in-line holder for Class CC fuses. A single #12
stranded copper wire, copper crimp, on the load side. A sin-
gle #4 stranded, copper wire, copper crimp on the line side.
Insulating boots are required.
1. Choose HEY- Series.
2. Choose âAâ for load side.
3. Choose âCâ for line side.
4. Choose 2A0660 insulating boots from page 2.
Complete Catalog Number: HEY-AC, 2A0660;
4 insulating boots required
per holder
#12 to #2
2
â¢
â¢
Y
Catalog Data â Insulating Boots
Catalog Numbers
2A0660
2A0661
Type
Single Conductor
Two Conductor
General Information:
⢠Insulating boots are not included with non-breakaway
parts and must be ordered separately. They come standard
with the breakaway series. The HEX-AW does not have the
boots. This catalog item does not have a breakaway receptacle.
⢠When boots are utilized, extra heat retention requires that
fuses are sized at a minimum of 200% of the RMS load
current.
Ordering Information:
HEX
HEY
Load
Terminal
Line
Terminal
Recommended Torque on Coupling Nut: 10-20 in-lb.
7-16-03
N03082
Form No. HEX & HEY Series
Page 1 of 2
Data Sheet: 2126
|
▷ |