English
Language : 

GBB-1-R Datasheet, PDF (1/2 Pages) Cooper Bussmann, Inc. – Ceramic Tube Fuses
1⁄4" x 1 1⁄4" Ceramic Tube Fuses
GBB Series, Very Fast-Acting
Description
• Very fast-acting
• Optional axial leads available
• 1⁄4" x 1 1⁄4" (6.3 x 32mm) physical size
• Ceramic tube, nickel-plated brass endcap construction
• 100pc-carton quantity weighs 1.0 lb (0.45 kg)
• UL Recognized product meets standard 248-14
Electrical Characteristics
Rated Current % of Amp Rating Opening Time
100%
None
1 - 20A
150%
250%
2 minutes maximum
1 seconds maximum
400%
-
100%
None
25, 30A
150%
250%
2 minutes maximum
6 seconds maximum
400%
-
Agency Information
• UL Recognized Card: 1-30A (JFHR2, E56412)
• CSA Component Accepted Card: 1-30A
(Class 1422-30 File 53787)
Ordering
• Specify packaging, product, and option code
Dimensions - mm/in
38.10
(1.500)
32.82
(1.292)
38.10
(1.500)
6.76
(0.266)
31.75
(1.250)
DIA. OF LEADS
0–15 AMP: 0.81
(0.032)
20–30 AMP: 1.02
(0.040)
6.35
(0.250)
Part Number
GBB-1-R
GBB-1-1/4-R
GBB-2-R
GBB-3-R
GBB-4-R
GBB-5-R
GBB-6-R
GBB-7-R
GBB-8-R
GBB-9-R
GBB-10-R
GBB-12-R
GBB-15-R
GBB-20-R
GBB-25-R
GBB-30-R
Voltage
Rating
Vac Vdc
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
250
125
Specifications
AC Interrupting
DC Interrupting
Rating (amps)*
Rating (amps)*
250Vac 125Vac
125Vdc
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200 10,000
10,000
200
200
200
200
200
200
200
200
200
Typical DC Cold
Resistance
(Ω)**
0.17750
0.17900
0.06620
0.04475
0.03175
0.02125
0.01800
0.01550
0.01360
0.01070
0.00934
0.00620
0.00472
0.00330
0.00252
0.00206
Typical
Voltage
Drop (V)‡
0.2096
0.2497
0.1687
0.1816
0.1778
0.1217
0.1324
0.1355
0.1144
0.1218
0.0877
0.0806
0.0735
0.0728
0.0610
0.0657
* Interrupting ratings: Interrupting ratings for 1-15A at 125Vdc was measured at 10,000A, 3.5 ms maximum, with time constant. Ratings 20-30A at 125Vdc were measured at 200A, 0.5
ms maximum, with time constant. Ratings 1-15A at 125Vac were measured at 10,000A, and 70% - 80% power factor. The interrupting ratings for 1-30A at 250Vac were measured at
90% - 100% power factor.
** DC Cold Resistance (Measured at <10% of rated current)
† Typical Melting I2t (I2t was measured at listed interrupting rating and rated voltage) Interrupting ratings were measured at 70% to 80% power factor on AC.
‡ Typical Voltage drop (Voltage drop was measured at 25°C±3°C ambient temperature at rated current)
0709 BU-SB09209
Page 1 of 2
Data Sheet 2013