English
Language : 

FWP-5A14F Datasheet, PDF (1/1 Pages) Cooper Bussmann, Inc. – FWP 660V/700V (IEC/U.L.)
Ferrule
FWP 660V/700V (IEC/U.L.) 1-50A
Bussmann®
®
Electrical Characteristics
Size
Rated
Current
RMS-Amps
I2t (A2S)
Pre-arc
Clearing
at 660V
1
—
—
2
—
—
3
—
—
4
—
—
5
1.6
11
6
—
—
14 ≈ 51mm
10
3.6
22
(·Ω¡§∑)
15
10
75
20
26
180
25
44
320
30
58
450
32
68
600
40
84
750
50
200
1800
Ⅲ Interrupting rating 200kA RMS Symmetrical.
Ⅲ Watts loss provided at rated current.
Ⅲ (700 Vdc/Interrupting rating 50kA) U.L. Recognition.
Ⅲ CSA Component Acceptance: 5 - 30A.
R
Dimensions
Fig. 1: 1-50 Amp Range
50.8
(2.000")
14.3
(0.563")
Watts
Loss
—
—
—
—
1.5
—
4
5.5
6
7
9
7.6
8
9
Ordering Information
Part
Number
FWP-1A14F
FWP-2A14F
FWP-3A14F
FWP-4A14F
FWP-5A14F
FWP-6A14F
FWP-10A14F
FWP-15A14F
FWP-20A14F
FWP-25A14F
FWP-30A14F
FWP-32A14F
FWP-40A14F
FWP-50A14F
Carton
Qty.
10
Carton
Weight
(kg)
Dimensions
Figure
Number
Curves
BIF #
0.225
Fig. 1
35785307
1 kg = 2.2 lbs. 1 lb = 0.45 kg
15.5
Dimension in mm.
(0.610")
1mm = 0.0394∑ 1∑ = 25.4mm
Electrical Characteristics
Total Clearing I2t
The total clearing I2t at rated voltage and
at power factor of 15% are given in the
electrical characteristics. For other volt-
ages, the clearing I2t is found by multi-
plying by correction factor, K , given as
a function of applied working voltage,
Eg, (RMS).
Arc Voltage
This curve gives the peak arc voltage,
UL, which may appear across the fuse
during its operation as a function of the
applied working voltage, Eg, (RMS) at a
power factor of 15%.
Power Losses
Watts loss at rated current is given in
the electrical characteristics. The curve
allows the calculation of the power
losses at load currents lower than the
rated current . The correction factor, Kp ,
is given as a function of the RMS load
current, Ib , in % of the rated current .
1.4
1.2 K
1.0
0.9
0.8
0.7
0.6
0.5 1)
0.4
2)
Eg
0.3
200 300 400 500 600 700
1) 5-30 Amp Range
2) 32-50 Amp Range
1.4
1.2 UL
103
9
8
7
6
5
4
Eg
3
200 300 400 500 600 700
1.0 Kp
0.8
0.6
0.5
0.4
0.3
0.2
0.1
Ib
30 40 50 60 70 80 90 100%
7-18-01
SB01191
The only controlled copy of this BIF document is the electronic read-only version located on the Bussmann
Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly
present comprehensive product data and provide technical information that will help the end user with design
applications. Bussmann reserves the right, without notice, to change design or construction of any products and
to discontinue or limit distribution of any products. Bussmann also reserves the right to change or update, without
notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested
by the user in all possible applications.
Form No.
Page 1 of 1
BIF Doc #720025