FRS-R-65_16 Datasheet, PDF (1/3 Pages) Cooper Bussmann, Inc. – Fusetron™ 600V Class RK5 | |||
|
Technical Data 1018
Effective May 2016
Supersedes July 2013
BUSSMANN
SERIES
Fusetron⢠600V Class RK5
FRS-R â 600 Vac/300 Vdc, 65-600 A, dual element, time-delay fuses
Catalog symbol:
⢠FRS-R-(amp)
Description:
Advanced protection, energy efficient Class RK5
dual element, current-limiting, time-delay fuses.
Time-delay â 10 seconds (minimum) at 500% of
rated current.
Specifications:
Ratings
⢠Volts â 600Vac, 300Vdc
⢠Amps â 65-600A
⢠Interrupting rating
⢠200 kA Vac RMS Sym
⢠20 kA Vdc
Agency information
⢠UL® Listed, Std. 248-12, Class RK5, Guide
JDDZ, File E4273
⢠CSA® Certified, C22.2 No. 248.12, Class
1422-02, File 53787
⢠CE
Catalog numbers (amps)
FRS-R-65
FRS-R-125
FRS-R-70
FRS-R-150
FRS-R-75
FRS-R-175
FRS-R-80
FRS-R-200
FRS-R-90
FRS-R-225
FRS-R-100
FRS-R-250
FRS-R-110
FRS-R-300
FRS-R-350
FRS-R-400
FRS-R-450
FRS-R-500
FRS-R-600
Features:
⢠Provides motor overload, ground fault
and short-circuit protection. When used in
circuits subject to surge currents such as
those caused by motors, transformers and
other inductive components, these fuses
can be sized close to full-load amps to give
maximum overcurrent protection
⢠The time-delay feature makes it possible
to use fuse amp ratings which are much
smaller than those of non-time delay
fuses. Considerable cost saving occurs by
permitting the use of smaller size switches,
panels and fuses themselves
⢠Provides a good degree of short-circuit
protection (greater current-limitation) to help
protect downstream components from high
fault currents
⢠Gives motor running back-up protection to
motors without extra cost
⢠Helps protect motors against burnout from
overloads and single-phasing when sized
properly
⢠Simplifies and improves blackout prevention
(selective coordination ratios)
⢠Dual-element fuses can be applied in
circuits subject to temporary motor
overloads and surge currents to provide
both high-performance, short-circuit and
overload protection
Dimensions - in:
A
B
Carton quantity
Amp ratings
65â100
101â200
201â400
401â600
Carton Qty.
1
1
1
1
Amp ratings
A
B
65-100
7.88
1.11
110-200
9.63
1.61
225-400
11.63
2.34
450-600
13.38
2.88
|
▷ |