English
Language : 

FRS-R-600 Datasheet, PDF (1/3 Pages) Cooper Bussmann, Inc. – FRS-R 600Vac/300Vdc, 65-600A, Dual Element, Time-Delay Fuses
FUSETRON™ 600V Class RK5
FRS-R — 600Vac/300Vdc, 65-600A, Dual Element, Time-Delay Fuses
Dimensions - in
A
B
Description: Advanced protection, energy efficient Class RK5
dual element, current-limiting, time-delay fuses. Time-delay –
10 seconds (minimum) at 500% of rated current.
Catalog Symbol: FRS-R-(amp)
Ratings:
Volts — 600Vac, 300Vdc
Amps — 65-600A
IR — 200kA Vac RMS Sym.
— 20kA Vdc
Agency Information:
CE, UL Listed, Std. 248-12, Class RK5, Guide JDDZ,
File E4273
CSA Certified, C22.2 No. 248.12, Class 1422-02, File 53787
Catalog Numbers (amps)
FRS-R-65
FRS-R-125
FRS-R-70
FRS-R-150
FRS-R-75
FRS-R-175
FRS-R-80
FRS-R-200
FRS-R-90
FRS-R-225
FRS-R-100
FRS-R-250
FRS-R-110
FRS-R-300
FRS-R-350
FRS-R-400
FRS-R-450
FRS-R-500
FRS-R-600
Carton Quantity and Weight
Amp Rating
Carton Qty.
65–100
1
101–200
1
201–400
1
401–600
1
Amp Ratings
65-100
110-200
225-400
450-600
A
7.88 (± 0.062)
9.63 (± 0.062)
11.63 (± 0.094)
13.38 (± 0.094)
B
1.11 (± 0.02)
1.61 (± 0.02)
2.34 (± 0.02)
2.88 (± 0.02)
Features:
• Provides motor overload, ground fault and short-circuit
protection. When used in circuits subject to surge currents
such as those caused by motors, transformers and other
inductive components, these fuses can be sized close to
full-load amps to give maximum overcurrent protection.
• The time-delay feature makes it possible to use fuse amp
ratings which are much smaller than those of non-time delay
fuses. Considerable cost saving occurs by permitting the
use of smaller size switches, panels and fuses themselves.
• Provides a good degree of short-circuit protection (greater
current-limitation) to help protect downstream components
from high fault currents.
• Gives motor running back-up protection to motors without
extra cost.
• Helps protect motors against burnout from overloads and
single-phasing when sized properly.
• Simplifies and improves blackout prevention (selective
coordination ratios).
• Dual-element fuses can be applied in circuits subject to
temporary motor overloads and surge currents to provide
both high-performance, short-circuit and overload
protection.
Recommended Fuse Blocks
Fuse Amps
1-Pole
2-Pole
70-100
RM60100-1CR RM60100-2CR
110-200
RM60200-1CR RM60200-2CR
225-400
RM60400-1CR RM60400-2CR
450-600
RM60600-1CR RM60600-2CR
3-Pole
RM60100-3CR
RM60200-3CR
RM60400-3CR
RM60100-3CR
For additional information on the RM Series of 600 volt fuse
blocks, see product brochure # 3192.
Fuse Reducers For Class R Fuses
Equipment
Desired Fuse
Fuse Clips
(Case) Size
200A
100A
400A
100A
200A
100A
600A
200A
400A
Catalog Numbers
(Pairs) 600V
NO.2621-R
NO.2641-R
NO.642-R
NO.2661-R
NO.2662-R
NO.2664-R†
† Single reducer only (pair not required).
For additional information on Class R fuse reducers, see
Data Sheet # 1118.
0713
BU-SB13729
Page 1 of 3
Data Sheet # 1018