FRN-R-70 Datasheet, PDF (1/4 Pages) Cooper Bussmann, Inc. – Fusetron™ FRN-R Class RK5 250Vac, 125/250Vdc 70-600A, dual element, time-delay fuses | |||
|
Technical Data1010
Effective February 2016
Supersedes July 2013
Fusetron⢠FRN-R Class RK5 250Vac, 125/250Vdc
70-600A, dual element, time-delay fuses
Catalog symbols:
⢠FRN-R-_
Description:
Eaton Bussmann® series advanced protection,
energy efficient FRN-R Class RK5 dual element,
current-limiting, time-delay fuses. Time-delay â 10
seconds (minimum) at 500% of rated current.
Specifications:
Ratings
⢠Volts
⢠250Vac
⢠125Vdc (110-200A)
⢠250Vdc (225-600A)
⢠Amps 70-600A
⢠Interrupting rating
⢠200kA Vac RMS Sym.
⢠20kA Vdc
Agency information
⢠UL Listed, Std. 248-12, Class RK5,
Guide JDDZ, File E4273
⢠CSA Certified, C22.2 No. 248.12,
Class 1422-02, File 53787
⢠CE
Catalog numbers (amps)
FRN-R-70
FRN-R-125
FRN-R-75
FRN-R-150
FRN-R-80
FRN-R-175
FRN-R-85
FRN-R-200
FRN-R-90
FRN-R-225
FRN-R-100
FRN-R-250
FRN-R-110
FRN-R-300
Carton Quantity:
FRN-R-350
FRN-R-400
FRN-R-450
FRN-R-500
FRN-R-600
Amp rating
70 â 100
110 â 600
Carton qty.
5
1
Features:
⢠Provides motor overload, ground fault and
short-circuit protection
⢠Helps protect motors against burnout from
overloads and single-phasing when sized
properly
⢠Simplifies and improves blackout prevention
(selective coordination)
⢠Dual-element fuses can be applied in circuits
subject to temporary motor overloads and surge
currents to provide both high performance
short-circuit and overload protection
⢠The overload element provides protection
against low level overcurrent of overloads and
will hold on inrush current which is five times
greater than the amp rating of the fuse for a
minimum of ten seconds
|
▷ |