English
Language : 

BK-GMT-X Datasheet, PDF (1/2 Pages) Cooper Bussmann, Inc. – Medium time delay, low breaking capacity
5mm x 20mm Fuses
GMC Series Medium Time Delay, Glass Tube
Description
• Medium time delay, low breaking capacity
• Optional axial leads available
• 5mm x 20mm physical size
• Glass tube, nickel-plated brass endcap construction
• Designed to UL/CSA 248-14
RoHS
2002/95/EC
ELECTRICAL CHARACTERISTICS
Rated Current % of Amp Rating Opening Time
100%
None
63mA - 10A
135%
60 minutes maximum
200%
2 minutes maximum
Agency Information
• UL Listed, Guide JDYX, File E19180, 63mA-6.3A
• UL Recognized Card: (7A-10A) Guide JDYX2,
File E19180
• CSA Certified, Class 1422-01, File E65063, 63mA-6.3A
• MITI Approval, 1A-10A
• CCC Approval, 500mA-6.3A
Ordering
• Specify packaging, product, and option code
• For -R option, drop mA or A from product code
(i.e. GMC-2-R)
Dimensions
⁄mm
(inches)
5.54mm
(±.20)
38.10mm
(±.38)
(± ±0.5)
21.10mm
(±.81)
5.2mm
(+0.1/-0.2)
38.10mm
(±.38)
0.65mm
(REF)
• Ratings above 6.3A have a 0.8mm diameter lead
• With TR2 packaging code, lead wire length is 19.05mm
Product Code
GMC-63mA
GMC-80mA
GMC-100mA
GMC-125mA
GMC-150mA
GMC-160mA
GMC-200mA
GMC-250mA
GMC-300mA
GMC-315mA
GMC-400mA
GMC-500mA
GMC-600mA
GMC-630mA
GMC-700mA
GMC-750mA
GMC-800mA
GMC-1A
GMC-1.25A
GMC-1.5A
GMC-1.6A
GMC-2A
GMC-2.5A
GMC-3A
GMC-3.15A
GMC-3.5A
GMC-4A
GMC-5A
GMC-6A
GMC-6.3A
GMC-7A
GMC-8A
GMC-10A
Voltage
Rating
AC
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
250V
125V
125V
125V
125V
125V
125V
125V
125V
SPECIFICATIONS
AC Interrupting
Typical DC Cold
Rating*
Resistance
250V
125V
(ohms)**
35A
10,000A
10.350
35A
10,000A
-
35A
10,000A
4.775
35A
10,000A
3.400
35A
10,000A
2.555
35A
10,000A
2.295
35A
10,000A
1.395
35A
10,000A
0.965
35A
10,000A
0.838
35A
10,000A
0.685
35A
10,000A
0.615
35A
10,000A
0.335
35A
10,000A
0.282
35A
10,000A
0.246
35A
10,000A
0.213
35A
10,000A
0.213
35A
10,000A
0.180
35A
10,000A
0.156
100A
10,000A
0.098
100A
10,000A
0.076
100A
10,000A
0.067
100A
10,000A
0.043
100A
10,000A
0.035
100A
10,000A
0.026
100A
10,000A
0.025
-
10,000A
0.022
-
10,000A
0.019
-
10,000A
0.014
-
10,000A
0.013
-
10,000A
0.012
-
200A
0.012
-
200A
0.009
-
200A
0.007
Typical
Pre-Arc I2t
AC†
0.0027
0.0050
0.0094
0.014
0.022
0.022
0.032
0.046
0.081
0.081
0.18
0.41
0.60
0.66
0.85
0.85
0.85
1.8
3.4
5.4
5.8
8.9
13
19
23
25
36
58
88
110
150
200
300
Maximum
Voltage
Drop (mV)‡
1400
1400
1200
1000
800
730
650
490
580
480
510
370
360
360
340
320
290
250
200
190
160
130
130
130
130
130
120
120
120
120
120
110
110
* Interrupting ratings: Interrupting ratings for 63mA - 6.3A were measured at 70% - 80% power factor on AC. The interrupting ratings for 7A - 10A were measured at 100% power factor on AC.
** DC Cold Resistance (Measured at <10% of rated current)
† Typical Pre-Arching I2t (I2t was measured at listed interrupting rating and rated voltage)
‡ Maximum Voltage drop (Voltage drop was measured at 20°C ambient temperature at rated current)