English
Language : 

BK-GMD-200MA Datasheet, PDF (1/2 Pages) Cooper Bussmann, Inc. – 5 x 20mm Fuses GMD Series,Time-Delay, Glass Tube
5 x 20mm Fuses
GMD Series,Time-Delay, Glass Tube
Description
• Time-delay, low breaking capacity
• Optional axial leads available
• 5 x 20mm physical size
• Nickel-plated brass endcap construction
• Designed to UL/CSA 248-14
Electrical Characteristics
Rated Current % of Amp Rating Opening Time
100%
None
100mA - 4A
135%
200%
60 minutes maximum
5 seconds minimum
2 minutes maximum
Agency Information
• UL Listed, Guide JDYX, File E19180
• UL Recognition Card (4A), Guide JDYX2, File E19180
• CSA Certified, Class 1422-01, File 53787
• PSE/JET, File 1641-31003-1001
Ordering
Specify product code
• Insert packaging code prefix before part number. E.g.
BK/GMD-250-R
Specify option code if desired
• For axial leads, insert “V” between catalog series and
amp rating. E.g. BK/GMD-V-250-R
Dimensions - mm
5.54mm
(±.20)
38.10mm
(±.38)
(± ( 0.5)
21.10mm
(±.81)
5.2mm
(+0.1/-0.2)
0.65mm
(REF)
(±.38)
• With TR2 packaging code, lead wire length is 19.05mm
Part Number
GMD-125-R
GMD-150-R
GMD-200-R
GMD-250-R
GMD-300-R
GMD-315-R
GMD-375-R
GMD-400-R
GMD-500-R
GMD-600-R
GMD-630-R
GMD-750-R
GMD-800-R
GMD-1-R
GMD-1.2-R
GMD-1.25-R
GMD-1.5-R
GMD-1.6-R
GMD-2-R
GMD-2.5-R
GMD-3-R
GMD-4-R
Voltage
Rating
Vac
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
250
Specifications
Interrupting Rating (amps) Typical DC
Typical
at Rated Voltage (50Hz) Cold Resistance Melting I2t
250 Vac
125 Vac
(Ω)**
(amps)†
35
10,000
8.125
0.043
35
10,000
6.065
0.046
35
10,000
5.190
0.200
35
10,000
3.455
0.4
35
10,000
3.215
0.650
35
10,000
2.400
0.890
35
10,000
1.625
0.890
35
10,000
1.505
1.2
35
10,000
1.0645
1.4
35
10,000
0.948
3.1
35
10,000
0.629
3.1
35
10,000
0.4425
4.7
35
10,000
0.4475
6.6
35
10,000
0.3065
12
100
10,000
0.299
16
100
10,000
0.1995
16
100
10,000
0.158
25
100
10,000
0.124
27
100
10,000
0.107
42
100
10,000
0.0905
94
100
10,000
0.0655
145
200
10,000
0.048
300
Typical
Voltage
Drop (mV)‡
1600
1200
1100
950
800
750
650
600
550
450
450
410
380
310
280
245
240
220
200
195
190
190
Agency Approvals
UL
PSE
CSA
JET
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
UR
X
* Interrupting ratings (Interrupting ratings for 125mA - 3A were measured at 70% - 80% power factor on AC. The interrupting ratings for 4A were measured at 100%
power factor on AC)
** Typical DC Cold Resistance (measured at <10% of rated current)
† Typical Melting I2t (I2t was measured at listed interrupting rating and rated voltage)
‡ Typical Voltage Drop (voltage drop was measured at 20°C ambient temperature at rated current)
0209 BU-SB08894
Page 1 of 2
Data Sheet 2019